Laserfiche WebLink
3. PIPING SUMP TESTING <br /> Company Name: B.Z. Service Station Maintenance <br /> Company Address: 1041 Triangle Ct.,West Sacramento,CA 95605 <br /> Credentials: ® CSLB Licensed Contractor ❑ SWRCB Licensed Tank Tester <br /> License Type: ICC License Number: 433159 <br /> Test Equipment Used: INCON TS-STS Equipment Resolution: O.000I <br /> Sump#DSL-1 Sump#DSL-2 Sump# Sump# <br /> Sump Diameter: 37.5" 37.5" <br /> Sump Depth: 47" 47" <br /> Sump Material: FBG FBG <br /> Height from Tank Top to Top of 23" 18" <br /> Highest Piping Penetration: <br /> Height from Tank Top to Lowest 27„ 17" <br /> Electrical Penetration: <br /> Condition of sump prior to testing: FAIR FAIR <br /> Portion of Sump Tested' 36" 35" <br /> Does turbine shut down when <br /> sump sensor detects liquid(both ®Yes❑No❑NA ®Yes❑No❑NA ❑Yes❑No❑NA ❑Yes❑No❑NA <br /> product and water)?* <br /> Turbine shutdown response time 6 SEC 6 SEC <br /> Is system programmed for fail-safe ®Yes❑No❑NA ®Yes❑No❑NA ❑Yes❑No❑NA ❑Yes❑No❑NA <br /> shutdown?' <br /> Was fail-safe verified to be ®Yes❑No❑NA ®Yes❑No❑NA ❑Yes❑No❑NA ❑Yes❑No❑NA <br /> operational?* <br /> Wait time between applying <br /> pressure/vacuum/water and starting 15 MIN 15 MIN <br /> test: <br /> Test Start Time: 12:57 12:57 <br /> Initial Reading(Ri): 3.1831 1.5652 <br /> Test End Time: 1:12 1:12 <br /> Final Reading(RF): 3.1827 1.5652 <br /> Test Duration: 15 MIN 15 MIN 15 MIN 15 MIN <br /> Change in Reading(RF-Ri): 0.0004 0 <br /> Pass/Fail Threshold or Criteria: 0.002 0.002 0.002 0.002 <br /> Test Result: ® Pass ❑ Fail ®Pass ❑ Fail ❑Pass ❑ Fail ❑Pass ❑Fail <br /> Was sensor removed for testing? ®Yes❑No❑NA ®Yes❑No❑NA ❑Yes❑No❑NA ❑Yes❑No❑NA <br /> Was sensor properly replaced and ®Yes❑No❑NA ®Yes❑No❑NA ❑Yes❑No❑NA ❑Yes❑No❑NA <br /> verified functional after testing? <br /> Comments— (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> Secondary Containment Test Results 3 of 4 <br />