Laserfiche WebLink
top half of the breakaway. When dowel pin and guide are aligned, continue squeezing tool grip <br /> until the breakaway halves join together. <br /> CAUTION: Reconnection can cause a small amount of gasoline to leak out of the <br /> breakaway. A towel wrapped loosely around the breakaway can help to <br /> minimize fuel spills. <br /> 7. Remove the shear pin (#787) located in the spare shear pin location of the breakaway and <br /> install in place of the original. <br /> 8. Torque the shear pin to 20 inch-pounds (- 1.5 ft-lbs). DO NOT OVER-TIGHTEN. <br /> 9. If available, install a shear pin (#787) in the spare shear pin location. <br /> 10. Remove the Breakaway Reconnection Clamp. <br /> 11. Proceed with the tests outlined in Section 1.4 of the Healy Systems Scheduled Maintenance. <br /> Figure 1 Figure 2 <br /> sz <br /> • Dowel Guide <br /> TO Clamp Shear Pin Bushing Hole <br /> ~ Dowel Pin Q synt_►ry <br /> I ��a' y annx�r+Av Shear Pin Installation <br /> �uaurns <br /> - _ THAN r-0 Les. <br /> �noN <br /> SPARE <br /> } yy <br /> -y Pui Spare Shear <br /> �KUosnnla,w.x. Pin <br /> Tool Grip Bott ,, <br /> Franklin Fueling Systems Website: htto://www.franklinfueling.com <br /> 3760 Marsh Road Email: sales@franklinfueling.com <br /> Madison, Wisconsin 53718 USA Telephone: 800-225-9787 <br /> ARB Approved Installation, Operation and Maintenance Manual Fax: 608-838-6433 <br /> HEALY <br /> f Franklin Fueling Systems <br /> B-3 <br /> CARE Approved IBM 0-Healy Breakaway Madel 8781VV-Executive Orders VR-281 and VR-282 <br />