VR-202-Z -3 Exhibit 2 <br /> Clean Air Separator Pressure Management System <br /> 1 . The Clean Air Separator is a passive gasoline storage tank ullage pressure <br /> management system, with no electrical requirements. The Clean Air Separator <br /> vapor integrity shall be evaluated using the test procedure outlined in Exhibit 4 <br /> of this Executive Order. <br /> a. The system shall be removed from service when the Clean Air Separator <br /> fails the leak decay test outlined in Exhibit 4. <br /> b. Unless there is maintenance or testing being conducted on the Clean Air <br /> Separator, the system shall be removed from service when the four ball <br /> valves are not locked in the positions shown in Figure 2-2 or 2-2H for <br /> normal Clean Air Separator operation. Figure 2-2 applies to vertical <br /> Clean Air Separator installations and Figure 2-21-1 applies to horizontal <br /> Clean Air Separator installations. <br /> 2. The Clean Air Separator shall be installed within 100 feet from the vent line(s), <br /> and the associated piping shall be sloped 1/8" per foot minimum toward the <br /> vent line(s). <br /> Permeator AT-150 Pressure Management System <br /> 1. The Permeator AT-150 is an active gasoline storage tank pressure management <br /> system. <br /> a. The system vapor integrity shall be evaluated when conducting TP-201 .3 in <br /> conjunction with Exhibit 8. It has zero allowable leak rate. <br /> b. The system shall be removed from service when the Permeator AT-150 fails the <br /> compliance test outlined in Exhibit 15. <br /> 2. The Permeator AT-150 shall be installed within 10 feet of the vent line(s) using 2" inner <br /> diameter steel piping. The associated piping shall be 1/8" per foot minimum <br /> slope toward the vent line(s). Low resistance ("straight-through") 2" ball valves <br /> should be plumbed into these connection points to allow for processor isolation. <br /> Figure 2-7A shows a typical Single Inlet with Single Return on a 2 UST system. <br /> Figure 2-8A shows a typical Single Inlet with Single Return on a 3 UST system. <br /> Figure 2-9A shows a typical Dual Inlet with Single Return on a 3 UST system. <br /> Figure 2-10A shows a typical Single Vent Inlet (Manifold at UST) with Single Return on <br /> Multiple UST system. <br /> 3. Typical installation of the Permeator AT-150 is to draw in the ullage air/vapor mixture <br /> from the UST system through the highest grade tank and to return a higher saturation <br /> vapor mixture to the lowest grade tank. The total piping distance from the highest <br /> grade tank to the vent line(s) shall be no longer than 90 feet with a minimum inner <br /> pipe diameter of 2". This configuration can work for GDF's with 2 or more UST's. <br /> Figure 2-713 shows a typical piping layout for Single Inlet with Single Return on a 2 UST <br /> system. <br />