Laserfiche WebLink
VR-202-Z -4 Exhibit 2 <br /> Figure 2-813 shows a typical piping layout for Single Inlet with Single Return on a 3 UST <br /> system. <br /> Figure 2-913 shows a typical piping layout for Dual Inlet with Single Return on a 3 UST <br /> system. <br /> Figure 2-10B shows a typical piping layout for a Single Vent Inlet (Manifold at UST) with <br /> Single Return on 3 UST system. <br /> 4. For GDF sites where the highest grade tank has a piping distance above 90 feet, <br /> it is permissible for a manifold of multiple UST's, regardless of fuel grade, provided <br /> that the total piping distance for one of the tanks in the manifold to the vent line(s) shall be <br /> no longer than 90 feet with a minimum inner pipe diameter of 2" for the draw in of ullage <br /> air/vapor mixture and there is still one lowest grade tank for the return of the higher <br /> saturation vapor mixture. See Figure 2-9A and Figure 2-913 for reference. <br /> 5. The Permeator AT-150 can only be operated on GDF installations that have the <br /> Veeder-Root Version 1.06 In-Station Diagnostics (ISD) software installed. <br /> 6. The Permeator AT-150 constantly logs oil level, processor on/off condition, vacuum <br /> level and tank pressure. <br /> 7. The Permeator AT-150 Programmable Logic Controller (PLC, display) constantly <br /> monitors PLC battery level and circuit continuity. <br /> 8. Except for testing, repairs or maintenance activities, the Permeator AT-150 shall be <br /> operating at all times with the ball valves in the `open' position with either the handles <br /> locked in place or the handles removed and locked inside the Permeator cabinet. <br /> 9. Maintenance requirements for the Permeator system are provided in the Permeator <br /> AT-150 Installation, Operation and Maintenance Manual that is part of the <br /> CARB-Approved Installation, Operation and Maintenance Manual and are summarized in <br /> the table below: <br /> Maintenance Interval Maintenance <br /> 5000 hours Drain and Replace Oil in Vacuum Pump <br /> Pressure/Vacuum Vent Valves for Gasoline Storage Tank Vents <br /> 1. All P/V vent valves shall be a CARB-certified P/V vent valve for a Phase I system. <br /> 2. At least one pressure/vacuum (P/V) vent valve shall be installed on each <br /> gasoline storage tank vent. The maximum number of P/V vent valves allowed <br /> and P/V vent valve performance specifications are listed in the applicable <br /> Phase I EVR Executive Order. Vent lines may be manifold to minimize the <br /> number of P/V vent valves and potential leak sources, provided the manifold <br /> conforms to all applicable fire regulations. At least one P/V vent valve shall be <br /> installed on vents if a manifold is incorporated. Figure 2-3 or 2-3H shows a <br /> typical manifold configuration for a single P/V vent valve with the Clean Air <br /> Separator. If two or more P/V vent valves are desired, they shall be installed in <br /> parallel, so that each can serve as a backup to the other if one should fail to <br /> open properly. Figure 2-4 or 2-4H shows a typical manifold configuration for <br /> two P/V vent valves installed in parallel with the Clean Air Separator. <br />