Laserfiche WebLink
VR-202-Z -5 Exhibit 2 <br /> Figure 2-5 or 2-5H shows a typical manifold configuration for three PN vent <br /> valves installed in parallel with the Clean Air Separator. Figure 2-6 or 2-6H <br /> shows a typical configuration for a PN vent valve mounted on a single 3" vent <br /> line with the Clean Air Separator. Figures 2-3, 2-4, 2-5 and 2-6 apply to vertical <br /> Clean Air Separator installations. Figures 2-31-1, 2-41-1, 2-51-1 and 2-61-1 apply to <br /> horizontal Clean Air Separator installations. <br /> Figures 2-7A, 2-8A, 2-9A and 2-10A show P/V configurations for the Permeator <br /> AT-150 installation options. <br /> Warranty <br /> Each manufacturer listed in Exhibit 1 shall include a warranty tag with the certified <br /> component(s). The manufacturer warranty tag, included with each component, shall be <br /> provided to the service station owner/operator at the time of installation. <br /> Vapor Recovery Piping Configurations <br /> NOTE: Vapor return piping shall meet the piping requirements specified <br /> in section 4.11 of CP-201. <br /> 1. Vapor Return and Vent Lines <br /> a. For facilities installed on or after April 1, 2003, all vapor return and vent <br /> lines shall be a minimum nominal internal diameter of 2 inches from the <br /> dispensers or the vent stacks to the first manifold. All lines after the first <br /> manifold and back to the underground storage tank shall have a minimum <br /> nominal internal diameter of 3 inches. <br /> Note: Facilities permitted by a local district prior to April 1, 2003 shall be <br /> required to meet the three inch diameter standard only upon facility <br /> modification which involves the addition, replacement, or removal of <br /> 50 percent or more of the buried vapor piping. <br /> After backfilling the vapor return and vent lines, the maximum pressure <br /> drop shall not exceed 0.5 inches WC at 60 cubic feet per hour as <br /> determined by TP-201.4, Dynamic Backpressure. The pressure drop shall <br /> be measured from the dispenser riser to the UST with pressure/vacuum <br /> vent valves installed and with the poppeted Phase I vapor connection <br /> open. <br /> b. For existing installations, the maximum pressure drop through the system <br /> shall not exceed 0.5 inches WC at 60 cubic feet per hour as determined by <br /> TP-201.4, Dynamic Backpressure. The pressure drop shall be measured <br /> from the dispenser riser to the UST with the pressure/vacuum vent valves <br /> installed and with the poppeted Phase I vapor connection open. <br /> Note: The V/L test from Exhibit 5 may be used to verify proper operation of the <br /> system, in lieu of measuring the pressure drop through the lines, provided <br /> that at least two gallons of product are introduced into the system through <br /> each dispenser riser, prior to the test. <br />