Laserfiche WebLink
VR-202-Z -6 Exhibit 2 <br /> 2. All vapor return lines shall have a minimum slope of 1/8 inch per foot from the <br /> dispenser riser to the riser of the underground storage tank (UST). A slope of 1/4 <br /> inch or more per foot is recommended wherever feasible. The vapor return path <br /> from any dispenser riser to the UST shall be free of liquid or fixed blockage. <br /> Exception: When it is not possible to achieve the necessary minimum slope <br /> from the dispenser back to the underground storage tanks, a low <br /> point Liquid Condensate Trap (i.e. knock out pot, thief port) can be <br /> utilized as long as the conditions under Liquid Condensate Traps <br /> in this Exhibit 2 are met. <br /> 3. The dispenser shall be connected to the riser with either flexible or rigid material <br /> that is listed for use with gasoline. The dispenser-to-riser connection shall be <br /> installed so that any liquid in the lines will drain toward the gasoline storage tank. <br /> The internal diameter of the connector, including all fittings, shall not be less <br /> than one-half inch (1/2"). <br /> Note: The dispenser-to-riser connection is defined as the piping connection <br /> between the outlet of the vapor flow meter and the inlet of the dispenser <br /> riser. A vapor shear valve may also be part of the riser connection. <br /> 4. There is no length restriction for the vapor return piping of the system as long as <br /> the system complies with the maximum pressure drop requirement of Item 1 (or <br /> the V/L option). <br /> 5. No product shall be dispensed from any fueling point at a GDF installed with the <br /> Assist Phase II EVR System Including In-Station Diagnostics (ISD) Systems if <br /> there is a vapor line that is disconnected and open to the atmosphere. <br /> Dispenser Vapor Piping <br /> 1. Any dispenser with a dispenser piping test valve in the closed position shall be <br /> considered a defect. <br /> 2. The ball valve shall be installed between the test port and the vacuum pump. <br /> The ball valve and test port shall be located on the inlet side of the vacuum <br /> pump. <br /> 3. If the vapor flow meter is installed below the vapor shear valve, then a "Y" fitting <br /> for introducing liquid shall be installed below the vapor flow meter. <br /> 4. The vapor flow meter shall be installed on the down stream side of the vacuum <br /> pump. <br /> 5. The Vapor Pressure Sensor shall be installed into one of the dispensers at the <br /> GDF located closest to the underground storage tanks (If a row of dispensers <br /> are equal distance from the gasoline tank pad and within 10' of each other, any <br /> dispenser can be used). <br />