Laserfiche WebLink
2—IN-1 SENSOR BOX(21 <br />J—BOX (TYP.) <br />2 SENSOR—NO TANK VACUUM SENSOR <br />ASSEMBLY KIT W/ MOUNTING BRACKET <br />SEAL—OFF (TYP.) (19 <br />1 FRP BONDED ENTRY FITTING <br />(TYP.) <br />1" MONITORING CONDUIT <br />(ROUTED TO INTERSTITIAL) C18]y <br />(ROBROY THROUGH SUMP ONLY) <br />2" BALL VALVE <br />48" DOUBLE WALL BRINE MONITORED <br />SUMP <br />CONTRACTOR TO INSTALL CLEVIS AND COTTER PIN <br />)4 VEEDER ROOT .1 GPH MAGNOSTRICTIVE PROBE TANK <br />LEVEL PROBE W/ TLS CAP & RING. OVERFILL ALARM <br />J5 SET © 90% CAPACITY. USE 4" FLOAT IN INSTALL KIT <br />_ LOOP VACUUM TUBING FROM <br />PRODUCT PIPING TO VAC SENSOR <br />1241" FRP BONDED ENTRY FITTING (TYP.) <br />1" HOMERUN TO BLDG. TURBINE POWER <br />18 (ROBROY THROUGH SUMP ONLY) <br />12 126 3" D.W. FRP BONDED ENTRY <br />FITTING & 4"x3" CONCENTRIC <br />REDUCER W/ TEST PORT & PLUG <br />4 148 3" OVER 2" FIBERGLASS <br />CROSSOVER CONTAINS VACUUM <br />TUBING ONLY FROM FILL SUMP <br />2"x24" FLEX (TYP.) 175 14 148 2 INSIDE 3" FRP PRODUCT LINE TO <br />DISPENSERS (VACUUM MONITORED) <br />SUMP LIQUID MONITORING SENSOR H 3" D.W. FRP BONDED ENTRY FITTING <br />(IN SENSOR HOLDER BELOW APEX 0 22" MANWAY 126 12 W/ 4"x3" CONCENTRIC REDUCER W/ <br />OF TANK AT LOWEST POINT) ci TEST PORT & VACUUM TUBING LOOPED <br />TO VAC SENSOR ASSEMBLY (TYP.) <br />NOTE: <br />SENSOR SHALL BE INSTALLED ON THE SAME SIDE OF PIPING <br />PENETRATIONS AS SHOWN <br />A: SECTION VIEW - DIESEL - ONE PUMP, ONE LINE <br />SCALE: 3/4" = 1'-0" <br />2" CAP. DRILL HOLES IN END AN INSTALL <br />GROMMETS FOR TUBING PASS THROUGH <br />1" MONITORING CONDUIT <br />(ROUTED TO INTERSTITIAL) 18 <br />(ROBROY THROUGH SUMP ONLY) <br />1" FRP BONDED ENTRY FITTING <br />(TYP.) <br />J—BOX (TYP.) <br />22" MANWAY <br />2 SENSOR—NO TANK VACUUM SENSOR <br />ASSEMBLY KIT W/ MOUNTING BRACKET <br />2 HP VARIABLE SPEED TURBINE W/ <br />3 GPH ELECTRONIC LEAK DETECTION <br />W/ SIPHON PORT FOR VACUUM SOURCE <br />LOOP VACUUM TUBING FROM <br />PRODUCT PIPING TO VAC SENSOR <br />2" BELLxMALE ADAPTER (TYP.) <br />3" OVER 2" FIBERGLASS CROSSOVER <br />CONTAINS VACUUM TUBING ONLY <br />FROM FILL SUMP <br />6) 3" D.W. FRP BONDED ENTRY <br />FITTING & 4"x3" CONCENTRIC <br />REDUCER W/ TEST PORT & PLUG <br />18 1" CONDUIT HOMERUN TO BLDG. TURBINE <br />POWER (ROBROY THROUGH SUMP ONLY) <br />1" FRP BONDED ENTRY FITTING (TYP.) <br />VEEDER ROOT .1 GPH MAGNOSTRICTIVE <br />PROBE TANK LEVEL PROBE W/ TLS CAP <br />& RING. OVERFILL ALARM SET © 90% <br />CAPACITY. USE 4" FLOAT IN INSTALL KIT <br />2"x24" FLEX (TYP.) <br />48" DOUBLE WALL BRINE <br />MONITORED SUMP <br />2" INSIDE 3" FRP PRODUCT LINE TO <br />DISPENSERS (VACUUM MONITORED) <br />3" D.W. FRP BONDED ENTRY FITTING <br />& 4"x3" CONCENTRIC REDUCER W/ <br />TEST PORT & VACUUM TUBING <br />LOOPED TO VAC SENSOR ASSEMBLY <br />(TYP.) <br />NOTE: THE LAST 2 FEET (MINIMUM) OF CONDUITS THAT <br />ENTER THE DOUBLE WALL SUMP SHALL BE PVC COATED <br />RIGID. <br />C: NOT USED <br />E: NOT USED <br />SCALE: NTS I SCALE: NTS <br />B: PLAN VIEW - DIESEL - ONE PUMP, ONE LINE D: NOT USED F: NOT USED <br />SCALE: 3/4" = 1'-0" SCALE: NTS SCALE: NTS <br />3/8 X 1/4 SS <br />BUSHING <br />INSTALLED AT <br />FACTORY <br />G: DOUBLE WALL TURBINE SUMP RISER (8-20"X-19" FLAT PANELS) <br />SCALE: NTS <br />FACTORY INSTALLED <br />*NOTE: <br />CONTRACTOR SHALL BE HELD RESPONSIBLE FOR PROPER INSTALLATION & <br />PREPARATION PER MANUFACTURERS INSTRUCTIONS AND SHALL REINSTALL <br />SUMPS IF HYDROSTATIC TESTING SHOWS LEAKING IN THIS AREA OF THE <br />SUMP. <br />SUMPS MUST BE ORIENTED SUCH THAT THE FACE OF THE SUMP PANEL IS <br />PARALLEL WITH ADJACENT TANK SUMP PANEL IN ORDER TO ACHIEVE THE 45' <br />ANGLES REQUIRED TO ROUTE THE PIPING WHILE MAINTAINING THE DESIRED <br />PERPENDICULAR ANGLE INTO THE SUMP. <br />O CONTRACTOR TO ADDITIONALLY GLASS WRAP & LAMINATE AT CONNECTION <br />FOLLOWING CURING OF ADHESIVE. SPECIFIC ATTENTION MUST BE GIVEN TO <br />SURFACE PREP AS TESTING REQUIREMENTS WILL DETECT THE SMALLEST OF <br />FLAWS. ALL MATERIALS MUST BE COMPATIBLE WITH GASOLINE, GASOLINE <br />WITH 15% MTBE (METHYL TERTIARY—BUTYL ETHER), OR GASOLINE WITH 10% <br />ETCH (ETHANOL). FIBERGLASS AND RESIN MUST EXTEND 1/2" BEYOND <br />COVERAGE OF ADHESIVE. <br />FIBERGLASS PIPING, 2" NOMINAL, BONDED TO SUMP <br />OR UDC INNER WALL USING GASOLINE COMPATIBLE <br />EPDXY RESIN. BOTTOM OF PIPE TO BE IN CONTACT <br />WITH LOWEST PART OF SUMP OR UDC. <br />CONTRACTOR TO BOND UNISTRUT CHANNEL TO <br />HOLDER TO ALLOW FIBERGLASS PIPE TO CLEAR <br />SUMP COLLAR "LIP". CONTRACTOR TO USE <br />GASOLINE—COMPATIBLE EPDXY TO BOND SPACER TO <br />SUMP AND PIPE. CONTRACTOR MAY USE UNISTRUT, <br />FIBERGLASS PIPE, OR ANY OTHER EQUIVALENT <br />MATERIAL THAT CAN WITHSTAND ENVIRONMENT OF <br />SUMP. <br />)R LIQUID <br />)E <br />DF <br />TURBINE SIDE SUMP SENSORS TO BE MOUNTEDJ <br />I <br />BELOW APEX OF TANK, AT BOTTOM OF SUMP AT <br />THICKEN CONCRETE SLAB TO <br />2 HP VARIABLE SPEED TURBINE W/ 105 10 <br />TANK <br />SUMP ARE MADE AND BELOW LOWEST PENETRATION <br />BELOW WHERE SECONDARY <br />3 GPH ELECTRONIC LEAK DETECTION <br />FIBERGLASS SUMP <br />DISPENSERS, PRODUCT PIPING CROSS CONNECTION <br />CONTAINMENT OF SUMP ENDS. <br />W/ SIPHON PORT FOR VACUUM SOURCE 109 0 <br />LIP <br />ARE DESIGNED TO ENTER THE SAME SIDE OF THE UNISTRUT <br />(TYP.). DIMENSION REQUIRED <br />SUMP AS SHOWN. IF PRODUCT PENETRATION CHANNEL <br />BONDED TO UNISTRUT <br />104 40" DIA. ACCESS <br />VARIES WITH FIELD CONDITIONS. <br />MINI HYDROSTATIC SENSOR IN BRINE <br />SEE NOTES BELOW <br />MANHOLE <br />FACTORY SUPPLIED RESERVOIR 1 <br />30" I.D. <br />18" <br />1-1/2" MIN. CROWN <br />(TYP.) <br />(NP. <br />(TYP. ALL OPENINGS) <br />. <br />H: SUMP SENSOR HOLDER DETAILS <br />�o <br />6" WIDE DETECTABLE <br />.d <br />0 <br />d <br />• <br />UNDERGROUND MARKING <br />•••'' 'd! •• ' <br />FESS /0 <br />••..d••• .•'• 'r <br />.~ <br />TAPE EMPIRE MAGNATEC <br />3" PEA GRAVEL MIN. TO <br />': ;. a; <br />CA��F� <br />% ` � <br />*4 .,.'• <br />..�►'. <br />#31-143 <br />•Q <br />PREVENT LOAD TRANSFER <br />o <br />Z <br />:'�' .:�� <br />(8 MIN. 12 MAX.) <br />TO TOP OF TANK <br />rn <br />jQQ� <br />QW <br />viz}< <br />SEAL OFF W/ DRAIN 191 <br />O z o <br />o <br />CCZ <br />(l I� cn� <br />207 TANK <br />GAUGE ADAPTER & CAP <br />2—IN-1 SENSOR BOX(21 <br />J—BOX (TYP.) <br />2 SENSOR—NO TANK VACUUM SENSOR <br />ASSEMBLY KIT W/ MOUNTING BRACKET <br />SEAL—OFF (TYP.) (19 <br />1 FRP BONDED ENTRY FITTING <br />(TYP.) <br />1" MONITORING CONDUIT <br />(ROUTED TO INTERSTITIAL) C18]y <br />(ROBROY THROUGH SUMP ONLY) <br />2" BALL VALVE <br />48" DOUBLE WALL BRINE MONITORED <br />SUMP <br />CONTRACTOR TO INSTALL CLEVIS AND COTTER PIN <br />)4 VEEDER ROOT .1 GPH MAGNOSTRICTIVE PROBE TANK <br />LEVEL PROBE W/ TLS CAP & RING. OVERFILL ALARM <br />J5 SET © 90% CAPACITY. USE 4" FLOAT IN INSTALL KIT <br />_ LOOP VACUUM TUBING FROM <br />PRODUCT PIPING TO VAC SENSOR <br />1241" FRP BONDED ENTRY FITTING (TYP.) <br />1" HOMERUN TO BLDG. TURBINE POWER <br />18 (ROBROY THROUGH SUMP ONLY) <br />12 126 3" D.W. FRP BONDED ENTRY <br />FITTING & 4"x3" CONCENTRIC <br />REDUCER W/ TEST PORT & PLUG <br />4 148 3" OVER 2" FIBERGLASS <br />CROSSOVER CONTAINS VACUUM <br />TUBING ONLY FROM FILL SUMP <br />2"x24" FLEX (TYP.) 175 14 148 2 INSIDE 3" FRP PRODUCT LINE TO <br />DISPENSERS (VACUUM MONITORED) <br />SUMP LIQUID MONITORING SENSOR H 3" D.W. FRP BONDED ENTRY FITTING <br />(IN SENSOR HOLDER BELOW APEX 0 22" MANWAY 126 12 W/ 4"x3" CONCENTRIC REDUCER W/ <br />OF TANK AT LOWEST POINT) ci TEST PORT & VACUUM TUBING LOOPED <br />TO VAC SENSOR ASSEMBLY (TYP.) <br />NOTE: <br />SENSOR SHALL BE INSTALLED ON THE SAME SIDE OF PIPING <br />PENETRATIONS AS SHOWN <br />A: SECTION VIEW - DIESEL - ONE PUMP, ONE LINE <br />SCALE: 3/4" = 1'-0" <br />2" CAP. DRILL HOLES IN END AN INSTALL <br />GROMMETS FOR TUBING PASS THROUGH <br />1" MONITORING CONDUIT <br />(ROUTED TO INTERSTITIAL) 18 <br />(ROBROY THROUGH SUMP ONLY) <br />1" FRP BONDED ENTRY FITTING <br />(TYP.) <br />J—BOX (TYP.) <br />22" MANWAY <br />2 SENSOR—NO TANK VACUUM SENSOR <br />ASSEMBLY KIT W/ MOUNTING BRACKET <br />2 HP VARIABLE SPEED TURBINE W/ <br />3 GPH ELECTRONIC LEAK DETECTION <br />W/ SIPHON PORT FOR VACUUM SOURCE <br />LOOP VACUUM TUBING FROM <br />PRODUCT PIPING TO VAC SENSOR <br />2" BELLxMALE ADAPTER (TYP.) <br />3" OVER 2" FIBERGLASS CROSSOVER <br />CONTAINS VACUUM TUBING ONLY <br />FROM FILL SUMP <br />6) 3" D.W. FRP BONDED ENTRY <br />FITTING & 4"x3" CONCENTRIC <br />REDUCER W/ TEST PORT & PLUG <br />18 1" CONDUIT HOMERUN TO BLDG. TURBINE <br />POWER (ROBROY THROUGH SUMP ONLY) <br />1" FRP BONDED ENTRY FITTING (TYP.) <br />VEEDER ROOT .1 GPH MAGNOSTRICTIVE <br />PROBE TANK LEVEL PROBE W/ TLS CAP <br />& RING. OVERFILL ALARM SET © 90% <br />CAPACITY. USE 4" FLOAT IN INSTALL KIT <br />2"x24" FLEX (TYP.) <br />48" DOUBLE WALL BRINE <br />MONITORED SUMP <br />2" INSIDE 3" FRP PRODUCT LINE TO <br />DISPENSERS (VACUUM MONITORED) <br />3" D.W. FRP BONDED ENTRY FITTING <br />& 4"x3" CONCENTRIC REDUCER W/ <br />TEST PORT & VACUUM TUBING <br />LOOPED TO VAC SENSOR ASSEMBLY <br />(TYP.) <br />NOTE: THE LAST 2 FEET (MINIMUM) OF CONDUITS THAT <br />ENTER THE DOUBLE WALL SUMP SHALL BE PVC COATED <br />RIGID. <br />C: NOT USED <br />E: NOT USED <br />SCALE: NTS I SCALE: NTS <br />B: PLAN VIEW - DIESEL - ONE PUMP, ONE LINE D: NOT USED F: NOT USED <br />SCALE: 3/4" = 1'-0" SCALE: NTS SCALE: NTS <br />3/8 X 1/4 SS <br />BUSHING <br />INSTALLED AT <br />FACTORY <br />G: DOUBLE WALL TURBINE SUMP RISER (8-20"X-19" FLAT PANELS) <br />SCALE: NTS <br />FACTORY INSTALLED <br />*NOTE: <br />CONTRACTOR SHALL BE HELD RESPONSIBLE FOR PROPER INSTALLATION & <br />PREPARATION PER MANUFACTURERS INSTRUCTIONS AND SHALL REINSTALL <br />SUMPS IF HYDROSTATIC TESTING SHOWS LEAKING IN THIS AREA OF THE <br />SUMP. <br />SUMPS MUST BE ORIENTED SUCH THAT THE FACE OF THE SUMP PANEL IS <br />PARALLEL WITH ADJACENT TANK SUMP PANEL IN ORDER TO ACHIEVE THE 45' <br />ANGLES REQUIRED TO ROUTE THE PIPING WHILE MAINTAINING THE DESIRED <br />PERPENDICULAR ANGLE INTO THE SUMP. <br />O CONTRACTOR TO ADDITIONALLY GLASS WRAP & LAMINATE AT CONNECTION <br />FOLLOWING CURING OF ADHESIVE. SPECIFIC ATTENTION MUST BE GIVEN TO <br />SURFACE PREP AS TESTING REQUIREMENTS WILL DETECT THE SMALLEST OF <br />FLAWS. ALL MATERIALS MUST BE COMPATIBLE WITH GASOLINE, GASOLINE <br />WITH 15% MTBE (METHYL TERTIARY—BUTYL ETHER), OR GASOLINE WITH 10% <br />ETCH (ETHANOL). FIBERGLASS AND RESIN MUST EXTEND 1/2" BEYOND <br />COVERAGE OF ADHESIVE. <br />FIBERGLASS PIPING, 2" NOMINAL, BONDED TO SUMP <br />OR UDC INNER WALL USING GASOLINE COMPATIBLE <br />EPDXY RESIN. BOTTOM OF PIPE TO BE IN CONTACT <br />WITH LOWEST PART OF SUMP OR UDC. <br />CONTRACTOR TO BOND UNISTRUT CHANNEL TO <br />HOLDER TO ALLOW FIBERGLASS PIPE TO CLEAR <br />SUMP COLLAR "LIP". CONTRACTOR TO USE <br />GASOLINE—COMPATIBLE EPDXY TO BOND SPACER TO <br />SUMP AND PIPE. CONTRACTOR MAY USE UNISTRUT, <br />FIBERGLASS PIPE, OR ANY OTHER EQUIVALENT <br />MATERIAL THAT CAN WITHSTAND ENVIRONMENT OF <br />SUMP. <br />)R LIQUID <br />)E <br />DF <br />TURBINE SIDE SUMP SENSORS TO BE MOUNTEDJ <br />I <br />BELOW APEX OF TANK, AT BOTTOM OF SUMP AT <br />FIBERGLASS <br />SIDE OF TANK WHERE PRODUCT PENETRATIONS INTO <br />TANK <br />SUMP ARE MADE AND BELOW LOWEST PENETRATION <br />DATE <br />FITTING WITHIN SUMP AREA. PRODUCT PIPING TO <br />FIBERGLASS SUMP <br />DISPENSERS, PRODUCT PIPING CROSS CONNECTION <br />INSIDE TANK COLLAR <br />BETWEEN SUMPS AND SIPHON PIPING PENETRATIONS <br />LIP <br />ARE DESIGNED TO ENTER THE SAME SIDE OF THE UNISTRUT <br />1. SENSOR HOLDER <br />SUMP AS SHOWN. IF PRODUCT PENETRATION CHANNEL <br />BONDED TO UNISTRUT <br />ENTERS ON BOTH SIDES OF SUMP DUE TO FIELD <br />CONDITIONS, THEN DUAL SENSORS AT TURBINE <br />CHANNEL <br />SUMP WILL BE REQUIRED TO BE INSTALLED. <br />2L <br />2. SENSOR HOLDER <br />AND UNISTRUT <br />CHANNEL BONDED TO <br />0 <br />SUMP WALL. DO NOT <br />PENETRATE SUMP! <br />H: SUMP SENSOR HOLDER DETAILS <br />SCALE: 1" = 1'-0" <br />NOTE: CONTRACTOR TO USE ADDITIONAL <br />GALVANIZED FITTINGS AS REQUIRED TO <br />MINIMIZE BENDS IN FLEXIBLE CONNECTORS <br />NOTE: INDICATES ITEMS FOUND ON <br />XX MATERIALS LIST SHEETS M.5.3.01 & M.5.3.02 <br />CLIENT: <br />4: bp <br />406k <br />llor <br />ARCO <br />BP WEST COAST PRODUCTS, LLC <br />NO. <br />DATE <br />DESCRIPTION <br />0 <br />0 <br />0 <br />4 <br />5 <br />2L <br />0 <br />0 <br />0 <br />�o <br />0 <br />SEAL: <br />FESS /0 <br />NO. 36475 <br />* XP. 6-30-22 <br />y CIVIL <br />CA��F� <br />z <br />w <br />75 <br />•Q <br />W cco <br />0)dz <br />o <br />Z <br />2w N <br />Z 0 r <br />6r) <br />ODZ <br />rn <br />jQQ� <br />QW <br />viz}< <br />I I w w2: <br />O z o <br />o <br />CCZ <br />(l I� cn� <br />UzDco <br />000 0 <br />gz <br />p Z N <br />wz0r <br />�w <br />zwz� <br />3 o U v <br />CZ6 <br />zq <br />w o w <br />a(D <br />o <br />z = <br />z IL <br />z <br />g <br />DEVELOPMENT INFORMATION: <br />SITE ADDRESS: <br />ADDRESS <br />2510 S. STATE HWY 99 W. FRONTAGE ROAD <br />SAN JOAQUIN COUNTY, CA 95205 <br />DESIGNED BY: <br />CHECKED BY: <br />DRAWN BY: <br />ER <br />DATE: <br />PROJECT NO: <br />10/24/2019 <br />DRAWING TITLE: <br />TURBINE SIDE SUMPS AND PIPING <br />INSTALLATION DETAILS <br />(SINGLE 2HP TURBINE) <br />SHEET NO: <br />