PIPE SUPPORT NOTES:GAS PIPES:PIPE 1" DIA. OR LARGER SHALL HAVE TRANSVERSE BRACING @14" O.C. (MAX.) AND LONGITUDNAL BRACING @ 20" O.C. (MAX.). PIPES LESS THAN 1" DIA. NEED NO BRACING.OTHER PIPES:PIPES 2-1/2" DIA. OR LARGER SHALL HAVE TRANSVERSE BRACING@ 16" O.C. (MAX.) AND LONGITUDNAL BRACING @ 32" O.C. (MAX.).PIPES LESS THAN 2-1/2" DIA. NEED NO BRACINGTYPICAL (ALL PIPES):FOR PIPES WHERE THE DISTANCE OF THE HANGAR (FROM TOPOF PIPE TO BOTTOM OF SUPPORT) IS LESS THAN 12", NO LATERALBRACING IS REQUIRED.38" THREADED RODREFER TO PIPE SUPPORTATTACHMENT DETAILTHIS SHEET1-1/2" x 1-1/2" x 18"STELL ANGLE LATERALBRACING PER CBCCHAPTER 16 REQUIREMENTSAND SMACNA STANDARDSINSULATIONHOT WATERGALVANIZED SHIELDAT INSULATIONADJUSTABLE BAND HANGAR,SEE SPECS FOR TYPEHANGAR ROD,SEE SCHEDULE FOR SIZEWROUGHT STEELCLEVIS HANGARSEE SPECS FOR TYPEPIPE HANGER SCHEDULEPIPE SIZEHANGARRODBOLT12" THRU 34"14"14"1" THRU 1-12"38"38"2" THRU 2-12"38"12"3"12"12"PIPE SUPPORT NOTES:GAS PIPES:PIPE 1" DIA. OR LARGER SHALL HAVE TRANSVERSEBRACING @ 14" O.C. (MAX.) AND LONGITUDNAL BRACING @20" O.C. (MAX.). PIPES LESS THAN 1" DIA. NEED NO BRACING.OTHER PIPES:PIPES 2-1/2" DIA. OR LARGER SHALL HAVE TRANSVERSEBRACING @ 16" O.C. (MAX.) AND LONGITUDNAL BRACING @32" O.C. (MAX.).PIPES LESS THAN 2-1/2" DIA. NEED NO BRACINGTYPICAL (ALL PIPES):FOR PIPES WHERE THE DISTANCE OF THE HANGAR (FROMTOP OF PIPE TO BOTTOM OF SUPPORT) IS LESS THAN 12",NO LATERAL BRACING IS REQUIRED.38" DIA. BOLTHANGAR RODCLIP, TYPICALSUPERSTRUT A-1200-HSCHANNEL, LENGTH AS REQUIRED38" THREADED RODSUPERSTRUT PIPECLAMP, TYPICAL38" THREADED RODREFER TO PIPESUPPORT ATTACHMENTDETAIL THIS SHEETPLANSECTIONSQUARE SCORIATED TOPWITH VANDAL PROOF SCREWFINISHED FLOORADJUSTABLE LEVEL CONTROLMEMBRANE. SEE SPECIFICATIONSFOR ADDITIONAL INFORMATIONCAST IRON RISERMAY EXTEND ASWASTE OR VENTWALLCHROME WALLCOVER AND SCREWPLUGGED TEEWITH CLEANOUTFINISH FLOOR18" C.I. BENDBALANCE OF PIPING1"3"AC UNITUNIONTRAP FORMED OF LONGRADIUS ELBOWSOPEN VENT TEESLOPE 18" PER FOOT TO DRAINSEE PLAN FOR CONTINUATIONNOTE:CONDENSATE TRAP TO BE PROVIDED FOR AC UNITSWHICH ARE NOT INTERNALLY TRAPPED, VERIFY1/2" COPPER TO FLOOR DRAINTRAP PRIMER CONNECTIONUNIONTRAP PRIMERBALL VALVEACCESS DOOR,12"X12" MIN. SIZE1/2"CWCW SUPPLY12" MIN. AFF1" MINIMUM AIR GAPP-TRAPNO-HUB COUPLING (TYP)FLOOR SINKGRATEDOME STRAINERDRAIN PIPEFINISH FLOORCONCRETE SLABCAST IRONWASTE PIPESEE PLANSFOR CONT.24 ga SHEET METAL FLASHINGWITH DRAW BAND TOPCONDENSATE LINE / VENT PIPESEE PLAN FOR SIZE, ATTACH TOSTRUCTURE PER SMACNA GUIDELINES4# LEAD FLASHINGFINISHED ROOFROOF STRUCTUREAND INSULATION1" X 18" RING CLAMP ANDSUPPORT BRACKETS.SECURE WITH14" DIA. x 2" LAG SCREWSWATERHEATERCAPWATERHEATERHWSSNGASCWSSSS MOUNTING BRACKETATTACH WATERHEATER(S) TO WALLPER MANUFACTURER'SSPECIFICATIONSEXHAUST FLUESEE MECHANICAL DRAWINGSAIR INLET FLUEZ-FLEXVERTICALCONDENSATEDRAIN, ROUTECONDENSATEDRAIN TUBE TOFLOOR SINK1-1/2" PRESSURERELIEF HEADER -TERMINATE OVERFLOOR SINKTHROUGH 6" AIR GAPBALL VALVE,TYPICALPRESSURE RELIEFVALVE SET AT 150LBSROUTE FULL SIZERELIEF TO 1-1/2"HEADER1-1/4" SIOUX CHEF TAILPIECEWITH 78" O.D. COPPERCONDENSATE CONNECTION78" FLEX CONNECTION HOSE34" CONDENSATE LINE FROMROOFTOP HVAC UNITREFER TO FLOOR PLANS FORDISPOSAL LOCATIONS, TYPICALCONDENSATE PIPE SHALL HAVE ASLOPE OF NOT LESS THAN 18" / FT.AND SHALL BE COPPERNEW CONCRETEEXISTING CONCRETE6"5"4"4"6"NEW CONCRETE SLABSEE DRAWING P-2.1 FOR SLAB THICKNESS ANDREINFORCEMENT REQUIREMENTSEXISTING 5" THICK CONCRETE SLABWITH #3 @ 18" O.C. EACH WAY15 mil. POLY VAPOR BARRIER OVER 4" ROCKOVER 90% COMPACTED SUB-GRADE#4 REBAR DOWEL @ 16" O.C.DRILL AND EPOXY GROUTAT EXISTING, TYPICALP-3.0SCALE:3" = 1'-0"1FLOOR CLEANOUTSCALE:NO SCALE2PIPE HANGERSCALE:NO SCALE3PIPE SUPPORTSCALE:3" = 1'-0"5PIPE HANGERSCALE:NO SCALE6CONDENSATE DRAINSCALE:3" = 1'-0"8VENT PIPE FLASHINGSCALE:3" = 1'-0"4FLOOR SINKSCALE:NO SCALE7TRAP PRIMERSCALE:1/2" = 1'-0"9CONDENSATE DRAINSCALE:3/4" = 1'-0"10WATER HEATER PIPINGSCALE:3" = 1'-0"11NEW TO EXISTING CONCRETEOFSHEETSTAF9/15/202020-162DRAWNAS SHOWNSCALEDATECHECKEDJOB NO.SHEETREVISIONSBYSLWPROJECT : <br />CLIENT : <br />LOCATION : <br />CRUMBL COOKIES <br />2624 W. KETTLEMAN LANE, #150 <br />LODI, CA 95242 <br />THEODORE J. BRANDVOLD, ARCHITECT <br />616 14th STREET, MODESTO, CA 95354 <br />PH (209) 571-8158 FAX (209) 571-8160 <br />JUST DOUGH IT RENEWAL DATEC-25449JATEO <br />DEONCE <br />SERLI <br />D <br />THEST <br />OFORNVTARCHITEC.BRANDLI ODACALIF6-30-21INTERIOR TENANT IMPROVEMENT <br />A.P.N.: 058-03-022