260500 ELECTRICAL WORK FOR COMMON RESULTS: 260573. ARC FLASH HAZARDS: �±
<br /> 4. MINIMUM CONDUIT SIZE SHALL BE 1/2"ABOVE GRADE AND 3/4" UNDERGROUND. LEGEND
<br /> 1. ELECTRICAL INSTALLATION SHALL COMPLY WITH TITLE 24, CALIFORNIA 1. PROVIDE WARNING LABEL ON ELECTRICAL EQUIPMENT OF POSSIBLE ARC FLASH HAZARDS PER
<br /> CODE OF REGULATIONS, INCLUDING THE FOLLOWING: 5. MINIMUM ACCEPTABLE CONDUITS ARE: C.E.C. 110.16.
<br /> TITLE 24, CCR, PART 2, 2019 CBC ® FLUORESCENT LIGHT FIXTURE, RECESSED MOUNT CAP. LETTER=TYPE
<br /> TITLE 24, CCR, PART 3, 2019 CEC A. GALVANIZED RIGID STEEL- FOR USE ON: 260943. INTERIOR LIGHTING CONTROL SYSTEM: FLUORESCENT LIGHT FIXTURE, SURFACE MOUNT SM. LETTER=SWITCHING
<br /> TITLE 24, CCR, PART 4, 2019 CMC (1) EXTERIOR WALL SURFACES. ® CEILING LIGHT FIXTURE NUMBER=CIRCUIT
<br /> TITLE 24, CCR, PART 9, 2019 CFC 1. PROVIDE A COMPLETE AND FULLY OPERATIONAL INTERIOR LIGHTING CONTROL SYSTEM FOR
<br /> TITLE 24, CCR, PART 6, 2019 CALIFORNIA ENERGY CODE B. GALVANIZED STEEL EMT FOR USE: INTERIOR LIGHTING AS SPECIFIED HEREIN AND SHOWN ON THE DRAWINGS. Z © RECESSED LIGHT FIXTURE
<br /> TITLE 24, CCR, PART 11, 2019 CALIFORNIA GREEN BUILDING STANDARDS CODE (1) CONCEALED IN INDOOR FINISHED SPACES. ®-1 WALL BRACKET LIGHT FIXTURE
<br /> ALL APPLICABLE LOCAL CODES (2) EXPOSED INSIDE ELECTRICAL & MECHANICAL ROOMS. 2. THE COMPLETE SYSTEM, INCLUDING ALL DEVICES SHALL BE IN COMPLIANCE WITH TH 2019
<br /> I r
<br /> CALIFORNIA ENERGY CODE. ® LIGHT FIXTURE ON EMERGENCY POWER CIRCUIT WITH INTEGRAL EMERGENCY BATTERY PACK
<br /> 2. ELECTRICAL CONTRACTOR SHALL VERIFY POWER, TELEPHONE AND CABLE TV SERVICES AT SITE PRIOR C. LIQUID TIGHT STEEL FLEX: ® LIGHT FIXTURE ON EMERGENCY POWER CIRCUIT WITH INTEGRAL EMERGENCY BATTERY PACK
<br /> TO BIDDING. SERVICES TO CONFORM TO UTILITY COMPANY REQUIREMENTS. ELECTRICAL CONTRACTOR (1) FOR FINAL CONNECTION TO OUTDOOR EQUIPMENT. LENGTH SHALL NOT EXCEED 36". 3. THE COMPLETE SYSTEM SHALL BE AS MANUFACTURED BY NLIGHT, WATTSTOPPER, OR ® RECESSED LIGHT FIXTURE POWER CIRCUIT WITH INTEGRAL EMERGENCY BATTERY PACK
<br /> SHALL ARRANGE FOR SERVICE INSTALLATIONS PER UTILITY COMPANY REQUIREMENTS AND PAY ALL GREENGATE CONSISTING OF:
<br /> CUSTOMER CHARGED SERVICE COSTS. COORDINATE WITH OWNER AND UTILITY COMPANY FOR SERVICE D. FLEXIBLE STEEL CONDUIT: EXIT LIGHT-HIGH LEVEL W M B
<br /> INSTALLATION. (1) FOR INDOOR FINAL CONNECTION TO RECESSED LIGHT FIXTURES. LENGTH SHALL NOT EXCEED 72". A. LUMINARIES WITH 0-10V DIMMING LED DRIVERS. A ALTERNATE DESIGNATION OF LIGHT FIXTURE SHOWING TYPE & LAMPS
<br /> (2) FOR INDOOR FINAL CONNECTION TO HVAC EQUIPMENT. LENGTH SHALL NOT EXCEED 36".
<br /> 3. CONTRACTOR SHALL PROCURE AND PAY FOR ALL PERMITS, LICENSES, ETC. REQUIRED TO CARRY ON B. WALL DIMMER SWITCHES THAT COMMUNICATE THROUGH ROOM CONTROLLERS. $ LIGHT SWITCH - SPST UP 48" U.O.N. FLUSH ARCHITECTS
<br /> AND COMPLETE THE WORK. E. "PVC" SCHEDULE 40: $' LIGHT SWITCH - 3-WAY
<br /> (1) FOR CONDUITS RUN UNDERGROUND AND FOR UNDER BUILDING SLAB. C OCCUPANCY SENSORS THAT COMMUNICATE THROUGH ROOM CONTROLLERS. DIMMER SWITCH
<br /> 4. PROVIDE ALL LABOR, MATERIALS, TOOLS, PLANT EQUIPMENT, TRANSPORTATION AND PERFORM ALL (2) CONDUIT STUBUPS THROUGH THE FLOOR OR GRADE SHALL BE IN PVC WRAPPED RIGID STEEL
<br /> OPERATIONS NECESSARY FOR ANY REASONABLE INCIDENTAL TO PROPER EXECUTION AND COMPLETION CONDUIT. PVC WRAPPING SHALL EXTEND 6"ABOVE FINISHED FLOOR OR GRADE. D WHERE LIGHT FIXTURES FALL UNDER THE PRIMARY AND SECONDARY DAYLIT ZONES AS DEFINED ® OCCUPANCY SENSOR LIGHT SWITCH
<br /> OF ALL"ELECTRICAL WORK"WHETHER SPECIFICALLY MENTIONED OR NOT; ALL AS INDICATED, SPECIFIED (3) NOT PERMITTED FOR WIRING ABOVE FINISHED FLOOR INSIDE BUILDINGS BY SECTION 130.1(d) AND THE TOTAL INSTALLED GENERAL LIGHTING POWER IN THE PRIMARY DAYLIT ZONE ITA ITI OCCUPANCY SENSOR LIGHT SWITCH W/MANNUAL SWITCH 5757 Pacific Avenue
<br /> HEREIN, AND/OR IMPLIED THEREBY TO CARRY OUT THE APPARENT INTENT THEREOF. IS NOT LESS THAN 120W (EXCEPTION #1 TO SECTION 130.1(d)2) SUCH LIGHT FIXTURES SHALL BE PROVIDED Suite 226
<br /> F. ALUMINUM CONDUITS, IMC CONDUITS OR ALUMINUM FITTINGS ARE NOT APPROVED FOR USE ON WITH AUTOMATIC DAYLIGHITNG CONTROLS IN ACCORDANCE WITH SECTION 130.1(d)(2)(D). �V 120 VOLT DUPLEX WALL OUTLET FOR VIEWBOX
<br /> 5. ALL MATERIALS SHALL BE NEW AND LISTED WITH THE UNDERWRITERS' LABORATORIES, INC., SHALL THIS PROJECT. -(D: 120 VOLT DUPLEX WALL OUTLET UP 18" U.O.N. Stockton, CA 95207
<br /> MEET THEIR REQUIREMENTS AND SHALL BEAR THEIR LABEL WHEREVER STANDARDS HAVE BEEN E. TIME BASED GATEWAY DEVICE THAT PROVIDES TIME-BASED SIGNAL TO ROOM CONTROLLERS FOR j* 120 VOLT FOURPLEX OUTLET
<br /> ESTABLISHED AND LABEL SERVICE IS REGULARLY FURNISHED BY THAT AGENCY. G. ALL CONDUIT FITTINGS SHALL BE MALLEABLE IRON/STEEL. ALL SPACES THAT CONTROLLED BY MOTION SENSORS TO AUTOMATICALLY SHUT-OFF LIGHTS AT THE END 2000 L Street
<br /> OF DAY 120V DUPLEX OUTLET MOUNTED AT +42" A.F.F. OR +4" ABOVE
<br /> 6. ELECTRICAL DRAWINGS ARE ESSENTIALLY DIAGRAMMATIC AND ALTHOUGH THE SIZE AND LOCATIONS H. COUPLING: Suite 125
<br /> OF EQUIPMENT ARE SHOWN TO SCALE WHEREVER POSSIBLE, CONTRACTOR SHALL MAKE USE OF ALL DATA (1) EMT COUPLING -APPLETON TWC-CS SERIES 4. ALL SYSTEM COMPONENTS SHALL BE UL LISTED. ALL SYSTEM CONTROL COMPONENTS SHALL BE COUNTERTOP AS APPLICABLE
<br /> IN ALL CONTRACT DOCUMENTS AND VERIFY THIS INFORMATION AT THE SITE. CONTRACTOR SHALL BE (2) EMT CONNECTOR-APPLETON TW-CSI SERIES APPROVED BY THE CALIFORNIA ENERGY COMMISSION. ® SPECIAL PURPOSE OUTLET. TYPE & RATING TO SUIT LOAD SERVED Sacramento, CA 95811
<br /> RESPONSIBLE FOR LAYING OUT AND INSTALLING HIS WORK TO AVOID INTERFERENCE WITH OTHER TRADES. (3) FLEX CONDUIT CONNECTOR-T&B "TITE BITE", INSULATED 101 120V DUPLEX OUTLET, HALF-SWITCHED, +18" A.F.F. U.O.N., FLUSH
<br /> (4) LIQUID TIGHT FLEX CONDUIT CONNECTOR-APPLETON "STB" SERIES UP TO 2", "ST" SERIES OVER 2". 5. ALL EQUIPMENT AND ITEMS OF CONTROL SHALL BE INSTALLED AND WIRED IN ACCORDANCE WITH -Cc 120V DUPLEX OUTLET ON EMERGENCY POWER CIRCUIT, +18" T 209.944.9110
<br /> 7. WORK SHOWN ON THE DRAWINGS TO BE INSTALLED UNDERGROUND SHALL BE INSTALLED AT LEAST 24" MANUFACTURER'S REQUIREMENTS. A.F.F. U.O.N., FLUSH F 209.944.5711
<br /> BELOW GRADE UNLESS OTHERWISE NOTED. BACKFILL IN 6"THICK, PROPERLY MOISTENED LAYERS, I. RIGID STEEL CONDUIT CONNECTED TO BOXES AND CABINETS SHALL BE FITTED WITH TWO
<br /> SOLIDLY PACKED AND IRON TAMPED TO A DENSITY NOT LESS THAN THAT OF ADJACENT, UNDISTURBED LOCKNUTS AND INSULATING BUSHING, OA"A" SERIES. PROVIDE GROUNDING BUSHING OZ "BL" SERIES 6. PROVIDE WALL OCCUPANCY SENSOR LIGHT SWITCHES WHERE SO SHOWN ON PLANS. SUCH GFI INDICATES GROUND FAULT INTERRUPTER OUTLET www.wmbarchitects.com
<br /> EARTH. RESTORE SURFACES, ROADWAYS, WALKS, CURBS, WALLS AND EXISTING UNDERGROUND WHERE LOCKNUTS AND BUSHING IS NOT USED. CONDUITS CONNECTED TO BOXES EXPOSED TO OCCUPANCY SENSOR SWITCHES SHALL BE SINGLE LEVEL AUTOMATIC "ON"/AUTOMATIC "OFF"AS SHOWN o TELEPHONE WALL OUTLET UP 18" U.O.N. FLUSH
<br /> INSTALLATIONS TO ORIGINAL CONDITION IN AN ACCEPTABLE MANNER. WEATHER/MOISTURE SHALL BE FITTED WITH WATERTIGHT SEALING HUBS OF STEEL OR MALLEABLE ON PLANS. SENSORS SHALL COMPLY WITH SECTION 110.9 OF THE ENERGY CODE. 0 COMPUTER SYSTEM WALL OUTLET UP 18" U.O.N. FLUSH
<br /> IRON WITH SEALING RING AND INSULATED THREAT, T& B 370 SERIES.
<br /> 8. ALL ELECTRICAL EQUIPMENT EXPOSED TO THE WEATHER SHALL BE LISTED FOR EXTERIOR USE. 7. THE SYSTEM SHALL AUTOMATICALLY SWITCH OFF ALL LIGHTS WHEN CONTROLLED SPACE Aw TELEPHONE WALL OUTLET UP 54" U.O.N. FLUSH
<br /> J. TYPE NM AND NMC CABLES SHALL NOT BE USED ON THIS PROJECT. BECOMES UNOCCUPIED AND SWITCH ON LIGHTS WHEN THE SPACE IS RE-OCCUPIED. ALL SENSORS SHALL m INTERCOM SYSTEM STATION HCS.
<br /> 9. ALL U.L. LISTED EQUIPMENT SHALL BE INSTALLED AS PER THEIR LISTING OR LABELING. BE PROVIDED WITH USER ADJUSTABLE TIME DELAY (15 SEC. TO 20 MINUTES) FOR"SWITCH-OFF" FUNCTION p JUNCTION BOX
<br /> Engineering
<br /> K. THE PROJECT DRAWINGS ARE LAID OUT USING SOLID CONDUITS AND CABLES PULLED THROUGH AND ADJUSTABLE SENSITIVITY.
<br /> 10. IN LOCATIONS WHERE ELECTRICAL EQUIPMENT WOULD BE EXPOSED TO PHYSICAL DAMAGE, SUCH CONDUITS. MC CABLES MAY BE UTILIZED AS DESCRIBED BELOW, WITH RESTRICTIONS NOTED. MTIME CLOCK 50 years
<br /> ENCLOSURES OR GUARDS SHALL BE SO ARRANGED AND OF SUCH STRENGTH AS TO PREVENT SUCH 8. LOW VOLTAGE WIRING IS NOT REQUIRED TO BE IN CONDUIT EXCEPT IN HARDLID CEILINGS WHERE @) MOTOR OUTLET MIN. SIZE=1/2"C
<br /> DAMAGE. (1) PRIOR APPROVAL OF OWNER/ARCHITECT OR ENGINEER REQUIRED. SUCH WIRES SHALL BE RUN IN CONDUIT. CONDUIT CONCEALED IN WALL OR CEILING TICS-NO OF 12 WIRES 4512 Feather River Dr#F,Stockton,CA 95219
<br /> 209-478-8270 1 www.hcs-eng.com
<br /> 11. CONFLICTS BETWEEN SPECIFICATIONS AND PLANS: (2) MC CABLES SHALL BE AS MANUFACTURED BY SOUTHWIRE TYPE EZ-MC DURACLAD TYPE WITH LIGHT 262417. PANELBOARDS: -�/b- CONDUIT WITH INSULATED GROUND WIRE NO TICS=2#12 U.O.N.
<br /> WEIGHT STEEL ARMOR AND INSULATED GREEN GROUNDING CONDUCTORS OR APPROVED EQUAL. _ _ - CONDUIT CONCEALED IN FLOOR OR UNDERGROUND GROUND NOT SHOWN ®Richard C.Smith,PE richard@hcs-eng.com
<br /> g
<br /> a. ANY CONFLICT BETWEEN ELECTRICAL SPECIFICATIONS AND ELECTRICAL PLANS; OR BETWEEN 1. UNITS SHALL BE FLUSH OR SURFACE MOUNTED AS INDICATED ON THE PANEL SCHEDULE, WITH THE UNLESS ISOLATED .corn
<br /> ELECTRICAL PLANS AND PLANS OF ANOTHER DISCIPLINE SHALL BE BROUGHT TO THE ATTENTION OF THE (3) SHALL BE USED FOR BRANCH CIRCUITS ONLY AS NOTED BELOW. NUMBER AND SIZE OF BREAKERS AS INDICATED ON THE PANEL SCHEDULE. SINGLE POLE, TWO POLE, AND �� FLEXIBLE CONDUIT FOR LIGHTING ABOVE CEILING oBhuendraPatel.PE bhupendra0hcs-en
<br /> Bhupendra
<br /> Elizabeth Aguilar elizabeth@hcs-eng.com
<br /> ENGINEER AND A RESOLUTION RECEIVED PRIOR TO PROCUREMENT OR INSTALLATION OF THE ITEM IN THREE POLE BREAKERS SHALL BE BOLT-ON TYPE. MULTIPLE POLE BREAKERS SHALL HAVE COMMON ® DISTRIBUTION PANEL
<br /> QUESTION. (a) CANNOT BE USED ANYWHERE EXPOSED. INTERNAL TRIP CONNECTION. SINGLE POLE BREAKERS SHALL NOT BE TIED AT HANDLES TO FORM LIGHTING PANEL PROJECT#2020.265
<br /> MULTIPLE POLE BREAKERS. THE PANEL DOORS SHALL BE DOOR-IN-DOOR CONSTRUCTION AND SHALL
<br /> b. IF THE CONTRACTOR PROCEEDS WITH THE WORK WITHOUT RECEIVING ANY RESOLUTION TO THE (b) LIGHTING: VERTICAL DROPS IN WALL FOR LIGHT SWITCHES FORM JBOX IN CEILING. HORIZONTAL HAVE FLUSH TYPE LOCKS, ALL LOCKS SHALL BE KEYED ALIKE AND HAVE TYPEWRITTEN DIRECTORIES o SIGNAL CABINET AS DESIGNATED
<br /> CONFLICT HE/SHE DOES SO AT HIS/HER OWN RISK AND SHALL RECTIFY THE WORK TO THE SATISFACTION RUNS IN CEILING SHALL BE IN SOLID STEEL CONDUITS. INDICATING FIXTURES, EQUIPMENT, OR OUTLETS SERVICE BY EACH BREAKER. PANELS SHALL HAVE 4E=P WALL MOUNT EMERGENCY LIGHT FIXTURE W/BATTERY BACKUP
<br /> OF THE ENGINEER AT NO ADDITIONAL COST TO THE OWNER OR ENGINEER. COPPER BUSSING. Gospel Center Rescue
<br /> 260500.01. HVAC SYSTEMS:
<br /> (c) POWER RECEPTACLES: 262726. WIRING DEVICES: O PUSH BUTTON. FUNCTION AS INDICATED ON FLOOR PLAN Mission Kitchen
<br /> (A) FOR UNDERGROUND HOMERUNS: SOLID CONDUIT VERTICAL RISER IN WALL FROM UNDERGROUND N1 DOOR OPERATOR, ELECTRIC. Remodel
<br /> 1. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH MECHANICAL CONTRACTOR FOR EXACT CONDUIT TO FIRST RECEPTACLE JBOX. THEN HORIZONTAL RUNS WITHIN WALLS TO OTHER 1. UNITS SHALL BE EQUAL TO THE DEVICES SET FORTH HEREIN, IN STANDARD COLORS (BROWN, ® LINE VOLTAGE CIRCUIT BREAKER, FLUSH
<br /> LOCATIONS OF ALL HVAC UNITS, DISCONNECTS AND DEVICES IN FIELD. COORDINATE ROOF PENETRATIONS RECEPTACLE BOXES IN MC CABLE. WHITE, GREY, BEIGE OR IVORY)AS SELECTED BY THE ARCHITECT: M LOW VOLTAGE MOTION SENSITIVE OCCUPANCY SENSOR, WALL MOUNT Stockton,San Joaquin CA 95203St.
<br /> FOR DISCONNECTS AND WEATHERPROOF OUTLETS WITH ELECTRICAL CONNECTION POINTS ON THE UNITS (B) FOR OVERHEAD HOMERUNS: VERTICAL DROPS FROM JBOX IN CEILING THEN HORIZONTAL RUNS A. WIRING DEVICES LEVITON # HUBBELL# P &S#
<br /> TO KEEP FLEXIBLE CONDUIT LENGTH TO A MINIMUM (36" MAXIMUM). VERIFY AND CONFIRM THE ACTUAL WITHIN WALLS TO OTHER RECEPTACLES. HORIZONTAL RUNS IN CEILING SHALL BE IN SOLID STEEL SINGLE POLE SWITCH, 15A 1201-2 HBL1201 PS15AC1 MOTION SENSITIVE OCCUPANCY SENSOR, CEILING MOUNT
<br /> MOUNTING LOCATION ON THE HVAC UNIT FOR THE DISCONNECT. ALL SERVICING OUTLETS ON THE ROOF CONDUITS. DOUBLE POLE SWITCH, 15A 1202-2 HBL1202 PS15AC2 © POWER PACK FOR OCCUPANCY SENSOR. MOUNT IN CEILING SPACE
<br /> OR OUTDOORS FOR HVAC UNITS SHALL BE WP/GFI. THREE WAY SWITCH, 15A 1203-2 HBL1203 PS15AC3
<br /> (d) NO OTHER USE IS PERMITTED WITHOUT SPECIFIC WRITTEN APPROVAL OF THE ARCHITECT OR DUPLEX CONV. OUTLET, 15A 5262 HBL5262 5262
<br /> 2. THE RATING OF THE DISCONNECT SHALL BE SUCH AS TO ENABLE THE LARGEST FUSE SIZE ON THE ENGINEER. DUPLEX CONV. OUTLET, 20A 5362 HBL5362 5362
<br /> UNIT NAMEPLATE TO BE INSTALLED IN THE DISCONNECT. PROVIDE FUSES OF THIS RATING. DUPLEX CONV. GFI OUTLET, 15A 6599 GF15 1595L
<br /> (4) ALL FITTINGS AND TERMINATIONS FOR THE MC CABLING SYSTEM SHALL BE METAL AND SUITABLE DUPLEX CONV. GFI OUTLET, 20A 6899 GF15 2095L
<br /> 3. FURNISH AND INSTALL ALL LINE VOLTAGE CONDUITS AND LINE VOLTAGE WIRING (LOW VOLTAGE AND LISTED FOR SUCH USE.
<br /> CONDUITS AND WIRING BY MECHANICAL)TO HVAC EQUIPMENT AND ASSOCIATED CONTROLS AND DEVICES 2. THE CONTROLLED OUTLET SHALL HAVE PERMANENT UNIQUE MARKING PROVIDED BY THE ABBREVIATIONS
<br /> AS SHOWN ON THE ELECTRICAL AND MECHANICAL PLANS, UNLESS OTHERWISE NOTED. (5) ALL SUPPORTS, ATTACHMENTS SPACING SHALL BE PER CEC 330.30. MANUFACTURER OF THE RECEPTACLE. GENERAL NOTES & LEGEND
<br /> 4. RUN ALL CONDUITS FOR ROOFTOP EQUIPMENT WITHIN CEILING SPACE BELOW. SURFACE CONDUIT (6) FOR MULTI-WIRE BRANCH CIRCUITS SUCH CABLES SHALL HAVE MULTIPLE NEUTRALS, ONE FOR 3. THE MOUNTING HEIGHTS OF LIGHT SWITCHES, RECEPTACLES AND CONTROLS SHALL BE MAXIMUM A.F.G. ABOVE FINISHED GRADE
<br /> RUNS ON THE ROOF ARE NOT PERMITTED ON THIS PROJECT. EACH CIRCUIT. 48" MEASURED TO THE TOP OF BOXES OR MINIMUM 16"TO THE BOTTOM OF BOXES. SEE "LEGEND" FOR A.F.F. ABOVE FINISHED FLOOR
<br /> ACTUAL MOUNTING HEIGHTS OF DEVICES. VERIFY HEIGHT WITH ARCHITECT WHERE AN ACTUAL MOUNTING
<br /> 5. DISCONNECTS SHALL NOT BE USED AS THROUGH RACEWAYS FOR WIRING NOT DIRECTLY SERVING 6. CONDUCTORS SHALL BE COPPER CONDUCTORS TYPE THHN/THWN UNLESS OTHERWISE NOTED HEIGHT IS NOT CALLED OUT ON PLANS. UG UNDERGROUND
<br /> THE DISCONNECTS. SERVICING OUTLETS SHALL NOT BE MOUNTED ON DISCONNECTS. OR REQUIRED BY CODE. WP WEATHERPROOF
<br /> 4. SINGLE RECEPTACLE SERVED BY INDIVIDUAL 20A BRANCH CIRCUIT DEDICATED TO THE OUTLET CO CONDUIT ONLY
<br /> 260500.02. SUBMITTALS: 7. ALL DEVICES, CONDUITS, RACEWAYS AND CABLES SHOWN ARE NEW TO BE PROVIDED UNLESS SHALL BE 20A RATED PER CEC 210.21(6)(1). ALL OTHERS SHALL BE 15A RATED.
<br /> OTHERWISE NOTED. C CONDUIT
<br /> 1. PROVIDE THE FOLLOWING SUBMITTALS FOR REVIEW AND APPROVAL. EACH SHALL BE SUBMITTED 5. ALL 15A AND 20A, 120V OUTLETS IN KITCHEN SHALL BE GFCI PER CEC 210.8(B)(2). LOCATE SUCH U.O.N. UNLESS OTHERWISE NOTED
<br /> SEPARATELY TO AVOID DELAYS IN THE REVIEW OF ONE SUBMITTAL IN HOLDING UP REVIEW OF THE 8. FLASH AND COUNTERFLASH ALL ITEMS PASSING THROUGH THE ROOF. OUTLETS SO THAT THEY ARE ACCESSIBLE AFTER APPLIANCES THAT ARE PLUGGED INTO THE OUTLETS AREQ ,OFESS/ON
<br /> REMAINDER. IN PLACE. NO. NUMBER R0 C. S�<�
<br /> 260551. INSTALLATION OF RACEWAYS AND FITTINGS MIN. MINIMUM
<br /> a. LIGHTING CONTROLS 6. ALL RECEPTACLES INSTALLED OUTDOORS SHALL BE WEATHERPROOF AND HAVE GROUND FAULT MAX. MAXIMUM No. E14303
<br /> bBASIC R ACEW
<br /> ELECTRICAL MATERIALS CONCEAL RACEWAYS
<br /> ARE SPECIFICALLY CALLY WITHIN
<br /> CEILINGS, WALLS, AND FLOORS EXCEPT WHERE EXPOSED CIRCUIT INTERRUPTER PROTECTION.
<br /> C.
<br /> 262726.02. DEVICE PLATES: W/ WITH �ECTR\cP
<br /> 2. WHERE CONDUIT IS ALLOWED TO BE EXPOSED, INSTALL THE CONDUIT PARALLEL WITH OR AT GFI GROUND FAULT INTERRUPTER 9TFoF CAS F
<br /> RIGHT ANGLES TO STRUCTURAL MEMBERS, WALLS, AND LINES OF THE BUILDING. 1. ALL DEVICE PLATES FOR INDOOR USE SHALL BE STAINLESS STEEL.
<br /> 260500.03. WORKING CLEARANCES FOR ELECTRICAL SWITCHGEAR: & AND
<br /> 3. INSTALL WHERE INDICATED, OR AS REQUIRED BY CODE, PULLBOXES AND JUNCTION BOXES OF 2. ALL DEVICE BOXES WHICH ARE INSTALLED IN FIRE RATED WALL ASSEMBLY AND IS PROVIDED WITH (e),(E) EXISTING
<br /> 1. PROVIDE WORKING SPACES FOR ELECTRICAL PANELS AND SWITCHGEAR TO COMPLY WITH CEC SUFFICIENT SIZE TO FACILITATE WIRING. BOXES SHALL BE SIZED TO PROPERLY ACCOMMODATE ALL A FIRE-STOPPING PUTTY PAD SHALL HAVE A BRUSHED STAINLESS STEEL COVERPLATE IN ACCORDANCE
<br /> 110.26. CONDUCTORS ENTERING SAME. WITH THE REQUIREMENTS OF THE PUTTY PAD. (R)) REMOVE
<br /> 2. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH ALL TRADES INVOLVED TO ENSURE THE 4. DO NOT INSTALL CONDUIT OR TUBING WHICH HAS BEEN CRUSHED OR DEFORMED. 3. DEVICE COVERS FOR SURFACE MOUNTED BOXES SHALL BE 1/2" RAISED STEEL PLATES. (RR) REMOVE, RELOCATE AND RECONNECT AT LOCATION SHOWNA.I.C. AMPERE INTERRUPTING CAPACITY
<br /> CLEARANCES REQUIRED BY ITEM 1 ABOVE ARE PROVIDED. GND. GROUND
<br /> 5. RUN CONDUCTORS OF SAME CIRCUIT IN SAME CONDUIT. RUN CONDUCTORS OF DIFFERENT 4. DEVICE COVERS FOR DEVICES LOCATED IN DAMP LOCATIONS SHALL COMPLY WITH CEC 406.9(A).
<br /> 260526. GROUNDING: VOLTAGE SYSTEMS IN SEPARATE CONDUITS. V VOLT
<br /> 5. DEVICE COVERS FOR DEVICES LOCATED IN WET LOCATIONS SHALL COMPLY WITH CEC 406.9(6). CKT. CIRCUIT
<br /> 1. GROUND AND BOND ALL EQUIPMENT AS REQUIRED BY GOVERNING CODES AND SPECIFICALLY 6. INSTALL NO CONDUCTORS UNTIL WORK WHICH MIGHT CAUSE DAMAGE TO SUCH CONDUCTORS
<br /> INCLUDING SWITCHBOARD, PANELBOARDS, MOTOR CASES, METAL PIPING SYSTEMS, STRUCTURAL STEEL, OR THE CONDUIT HAS BEEN COMPLETED. 262729. DISCONNECT SWITCHES: KW KILOWATT PUBLISH HISTORY:
<br /> ETC. KVA KILOVOLT AMPERE
<br /> 7. KEEP ALL CONDUITS AT LEAST SIX INCHES AWAY FROM THE COVERING ON HOT WATER OR STEAM 1. UNITS SHALL BE HEAVY DUTY FUSED DISCONNECT SWITCHES, TWO OR THREE POLE TYPE, WHERE VNo.SPACE DATE PURPOSE
<br /> 2. PROVIDE GROUND WIRES IN ALL FEEDERS AND BRANCH CIRCUITS, SIZE PER CEC TABLE 250.122 PIPES. INDICATED ON THE DRAWINGS, OR AS REQUIRED BY CODE. SWITCHES AND FUSES SHALL BE AS REQUIRED SP
<br /> BY THE LOADS SERVING. CU COPPER A2/16/21 PLAN CHECK
<br /> 3. ALL GROUND WIRES SHALL BE INSULATED GROUND WIRES. 8. CAP RACEWAY ENDS DURING CONSTRUCTION. CLEAN OR REPLACE CONDUITS IN WHICH WATER AL ALUMINUM
<br /> OR FOREIGN MATTER HAVE ACCUMULATED, TO THE SATISFACTION OF THE ARCHITECT. 2. DISCONNECTS FOR FRACTIONAL HORSE POWER MOTORS SHALL BE MOTOR-RATED TOGGLE TYPE
<br /> 260533. PULL OR JUNCTION BOXES: DISCONNECTS. LC LIGHTING CONTACTOR
<br /> 9. CONDUITS SHALL BE SUPPORTED WITH STRAPS, WITH GALVANIZED MALLEABLE SPLIT RING AND NL NIGHT LIGHT
<br /> 1. INSTALL WHERE INDICATED, OR AS REQUIRED BY CODE, PULL BOXES AND JUNCTION BOXES OF ROD FOR INDIVIDUAL RUNS OR WITH KINDORF OR UNISTRUT CHANNEL SUPPORTS FOR MULTIPLE RUNS. 3. DISCONNECTS FOR SINGLE PHASE MOTORS SHALL BE SINGLE PHASE AND NOT THREE PHASE. PB PULLBOX
<br /> SUFFICIENT SIZE AND CAPACITY TO FACILITATE ALL WIRING. BOXES SHALL BE SIZED TO PROPERLY DISTANCE BETWEEN SUPPORTS SHALL NOT EXCEED 10 FEET. CONDUITS SHALL BE SUPPORTED
<br /> ACCOMMODATE ALL CONDUCTORS ENTERING SAME. INDEPENDENTLY OF ONE ANOTHER. 4. LOCATE DISCONNECTS IN ACCORDANCE WITH CEC 430.102. ENSURE ALL CODE-REQUIRED E.C. ELECTRICAL CONTRACTOR
<br /> 2. BOXES SHALL BE OF THE SHAPE AND SIZE BEST SUITED FOR THE PARTICULAR APPLICATION AND 10. CONDUITS CONNECTED TO BOXES AND CABINETS SHALL BE FITTED WITH TWO LOCKNUTS AND CLEARANCES. G.C. GENERAL CONTRACTOR
<br /> SHALL BE SUPPORTED DIRECTLY TO STRUCTURAL MEMBERS, FRAMING OR BLOCKING BY MEANS OF INSULATED BUSHING, OA"A" SERIES. 265100. LIGHTING: P.C. PLUMBING CONTRACTOR
<br /> SCREWS, ANCHORS, BOLTS OR EMBEDDED IN MASONRY. M.C. MECHANICAL CONTRACTOR
<br /> 11. CONDUITS NOT CONNECTED WITH LOCKNUTS AND BUSHINGS SHALL BE FITTED WITH GROUNDING 1. ALL LUMINARIES SHALL BE CERTIFIED BY THE MANUFACTURER TO THE CALIFORNIA ENERGY
<br /> A. SWITCH AND RECEPTACLE BOX SHALL BE ONE PIECE DRAWN OR STAMPED STEEL BOXES BUSHING, OZ"BL" SERIES, U. L. APPROVED AND BONDED. COMMISSION:
<br /> MINIMUM SIZE SHALL BE FOUR INCHES (4") SQUARE. BOXES SHALL BE FITTED WITH FLUSH DEVICE
<br /> COVERS, PLASTER RINGS, OR TILE SWITCH RINGS IN MASONRY IN AREA WHERE EXPOSED WIRING IS 12. CONDUIT STRAPS FOR INDIVIDUAL RUNS SHALL BE SECURED BY TOGGLE BOLTS ON HOLLOW A. ALL LUMINARIES SPECIFIED ON THIS PROJECT SHALL BE AS NOTED IN THE "LIGHT FIXTURE
<br /> PERMISSIBLE, BOXES SHALL BEFITTED WITH SURFACE TYPE COVERS. MASONRY, EXPANSION ANCHORS ON SOLID CONCRETE OR MASONRY, MACHINE SCREWS OR BOLTS ON SCHEDULE" ON THESE PLANS. NO SUBSTITUTES ARE PERMITTED WITHOUT WRITTEN APPROVAL OF THE
<br /> METAL SURFACES AND WOOD SCREWS ON WOOD CONSTRUCTION. THE USE OF NAILS TO ANCHOR ENGINEER.
<br /> B. WEATHERPROOF BOXES SHALL BE APPLETON FD SERIES AND FITTED WITH GASKETED CAST STRAPS ON WOOD CONSTRUCTION IS PROHIBITED. STRAPS SHALL BE TWO HOLE MALLEABLE IRON OR
<br /> COVERS. SNAP-TYPE STEEL WITH RIBBED BACK, GALVANIZED OR CADMIUM PLATED. THE USE B. ALL INTERIOR LUMINARIES SHALL BE PROVIDES WITH 0-10V DIMMING LED DRIVERS.
<br /> C. VOICE/DATA OUTLET BOXES SHALL BE 4 11/16"SQ.x2 1/8" DEEP MINIMUM, FITTED WITH PLASTER 13. PLACEMENT OF ALL BOXES SHALL BE GOVERNED BY APPLICABLE ARCHITECTURAL AND C. ALL EXTERIOR LUMINARIES SHALL BE PROVIDED WITH 0-10V DIMMING LED DRIVERS WITH
<br /> RINGS. STRUCTURAL REQUIREMENTS. INTEGRAL MOTION SENSORS WHERE SO NOTED.
<br /> D. BOXES FOR SPECIAL EQUIPMENT SHALL BE SUITABLE FOR THE PARTICULAR EQUIPMENT. 14. CONDUIT FITTINGS: EXCEPT WHERE OTHERWISE NOTED, CONDUIT FITTINGS SHALL BE APPLETON
<br /> OR APPROVED EQUAL. UNILETS SHALL BE MALLEABLE IRON AND FITTED WITH COVERS AND GASKETS.
<br /> E. BOXES SHALL BE LOCATED AND PLACED ACCORDING TO ARCHITECTURAL AND STRUCTURAL WMB PROJECT:
<br /> REQUIREMENTS. 15. TELEPHONE AND SIGNAL CONDUIT BENDS WHERE REQUIRED SHALL HAVE A RADIUS OF TEN TIMES
<br /> THE CONDUIT TRADE SIZE. 20-042
<br /> 260550. WIRING METHODS: LINE VOLTAGE SYSTEMS (120V AND ABOVE):
<br /> 16. PROVIDE PULL TAPE IN ALL EMPTY CONDUITS.
<br /> 1. ALL WIRING SHALL BE INSTALLED IN CONDUITS. CONDUITS SHALL BE RUN CONCEALED IN WALLS
<br /> AND CEILINGS WHERE FEASIBLE. ALL CONDUITS INSTALLED SURFACE ON WALL SHALL BE PAINTED TO 260553. NAMEPLATES & IDENTIFICATION:
<br /> MATCH WALL FINISH. MOUNT EXTERIOR CONDUITS ON WALL ON GALVANIZED UNISTRUTS. ALL SURFACE
<br /> CONDUIT INSTALLATION/RUNS SHALL BE APPROVED BY THE ARCHITECT PRIOR TO INSTALLATION. 1. INSTALL ENGRAVED NAMEPLATES FOR EACH PANELBOARD, CABINET, DISCONNECT, ETC. E O■ 1
<br /> NAMEPLATES SHALL BE SECURELY FASTENED TO THE EQUIPMENT WITH #4 PHILLIPS ROUND HEAD
<br /> 2. ALL CONDUITS RUN WITHIN INTERIOR FINISHED SPACES SUCH AS OFFICES, BREAKROOM, CADMIUM PLATED SELF-TAPPING SCREWS, BRASS BOLT.
<br /> RESTROOM ETC. SHALL BE RUN CONCEALED.
<br /> 2. PROVIDE CIRCUIT LABEL INDICATING PANEL AND CIRCUIT NUMBER ON EACH COVERPLATE FOR
<br /> 3. ALL CONDUITS RUN IN DEDICATED ELECTRICAL AND MECHANICAL ROOMS SHALL BE RUN EACH RECEPTACLE AND LIGHT SWITCH, MOTION SENSOR SWITCH. SUCH LABEL SHALL BE SELF ADHESIVE
<br /> EXPOSED. WHITE TAPE WITH BLACK LETTERS MADE ON A LABEL MAKER.
<br /> 3. ALL CONTROLLED RECEPTACLES SHALL BE PERMANENTLY MARKED TO DIFFERENTIATE THEM
<br /> FROM UNCONTROLLED RECEPTACLES PER CALIFORNIA ENERGY CODE SECTION 130.5(d)(3).