Laserfiche WebLink
  <br />  <br />SP 35  <br />  <br />III. T & B “Tite‐Bite” insulated connectors.  <br />IV. Suitable for connection of recessed fixtures, controls, and  <br />mechanical equipment.    <br />V. Not permitted where exposed to weather or other wet or  <br />corrosive conditions.  <br />VI. Length shall be a practical minimum, but to allow for  <br />movement of equipment connected without restricting  <br />flexibility of conduit.  <br />  <br />d. Liquid tight Flexible Metal Conduit (Sealtight):  <br />I. Minimum trade size of half (1/2”) inch.  <br />II. Appleton STB Series connectors through 2‐inch trade size and  <br />ST Series with insulated bushings in larger sizes.  <br />III. Length shall be practical minimum, but to allow for movement  <br />of equipment connected without restricting flexibility; not to  <br />exceed 72‐inches.  <br />  <br />e. Polyvinyl Chloride Schedule 40 (PVC‐40):  <br />I. Minimum trade size of three‐fourths (3/4”) inch.  <br />II. Joints shall be solvent welded per manufacturer's  <br />requirements.  <br />III. All portions shall be below grade. Minimum burial depth to be  <br />thirty‐six (36”) inches.  <br />IV. Not suitable for conduit stub for future extension.  <br />V. A copper bonding conductor shall be pulled in each power  <br />raceway and bonded to equipment at each end with approved  <br />lugs.  <br />VI. Continuation of run above concrete slab or into building  <br />interior from underground shall be with rigid steel elbow and  <br />bend.  <br />VII. Connection to steel conduit shall be made with approved  <br />threaded adapters.  <br />VIII. Seal around conductors at both ends of conduit.  <br />  <br />f. Surface Wiremold: