  <br />  <br />SP 37  <br />  <br />l. Conduits shall be capped during construction.  <br />m. Cap and provide pull wires in empty conduits.  Pull wires shall be  <br />#12 TW in conduits 1‐inch and smaller, and three sixteen (3/16”)  <br />inch polypropylene rope in conduits 1‐1/4” and larger.  <br />n. Seal underground conduits at both ends with wire jacket‐friendly  <br />compound.  <br />  <br />3. Boxes and Fittings:  <br />a. Boxes shall be of the shape and size best suited for the equipment  <br />and application, and shall be supported directly to structural  <br />members, framing, or blocking by means of screws, anchors, and  <br />bolts or embedded in masonry.  <br />b. In public areas use tamperproof steel cover plates with Torx head  <br />screws.  Emergency equipment must be tamperproof and keyed  <br />to conform to owner’s standard.  <br />c. Switch and receptacle box shall be one piece drawn steel boxes.  <br />d. Weatherproof boxes shall be Appleton FD Series and fitted with  <br />gasketed cast covers.  <br />e. Boxes for special equipment shall be as shown on plans and per  <br />manufacturer recommendations.  Coordinate approval and paint  <br />with owner before purchase.  <br />f. Install where indicated, or as required by Code, pull boxes, and  <br />junction boxes of sufficient size and capacity to facilitate all  <br />wiring.  Boxes shall be sized to properly accommodate all  <br />conductors entering same.  Make continuous wire runs without  <br />underground splices.  <br />g. Furnish all necessary foundations, supports, backing, etc., for all  <br />electrical enclosures and equipment.  Attach all boxes, cabinets,  <br />etc., to wood with wood or lag screws, to metal with machine  <br />screws or bolts, and to concrete with expansion anchors and  <br />machine screws or bolts.  <br />h. Electrical lighting fixtures shall be mounted using the  <br />manufacturer’s recommended mounting support; consult  <br />structural engineer of record.    <br />i. Provide warning signs where there is a hazardous exposure  <br />associated with access to or operation of the electrical equipment  <br />installed; at minimum place ‘High Voltage Shock Hazard’ labels on  <br />480V equipment and all panelboards.   <br />