Laserfiche WebLink
  <br />  <br />SP 38  <br />  <br />4. Conductors and Splices:  <br />a. Deliver to the site in unbroken packages, plainly marked with the  <br />manufacturer’s name, date of manufacture (not more than six  <br />months old), voltage, size, and classification number printed  <br />clearly every 12‐inches.    <br />b. Insulated Class B stranded copper type THHN/THWN and Direct  <br />Burial rated low voltage com wire; all 90‐degree C, 600 Volts.  <br />c. Minimum size of all conductors shall be #12 AWG unless  <br />otherwise indicated on the drawings.  <br />d. Conductors shall be as manufactured by Anaconda, General  <br />Electric, Rome Cable, Belden, Alpha Co., or equal.  <br />e. Neutral conductors for feeders and branch circuits shall be white  <br />and of the same size as the line conductors.  <br />f. Splices of #10 AWG and smaller, including fixture tape, shall be  <br />made with 3M Scotchlok connectors, T&B “Piggys”, Ideal  <br />Wingnuts, or equal.  <br />g. Splices of #8 AWG through #4 AWG shall be copper split bolt  <br />service connectors by Anderson, Blackburn, Burndy, or Panduit,  <br />insulated with Scotch #88 tape over Scotchfil electrical insulation  <br />putty.  <br />h. Splices of #2 AWG and larger shall be O‐Z XW Series insulated with  <br />Scotch #88 tape over Scotchfil electrical insulation putty.  <br />i. If allowed, splices in underground pull boxes shall be Scotchcast  <br />cast resin used with devices listed for intended use.  <br />j. Wire splicing devices shall be sized in accordance with the  <br />manufacturer’s recommendations.  <br />k. Typically, conductors shall be run in one continuous length.  <br />l. Conductors in panels, motor control centers, etc., shall be laced  <br />with T&B Ty‐raps.  <br />m. Self‐lubricant wire is desirable.  If lubricant is needed, use  <br />powdered soapstone, Y‐er EAS, Minerallac “Pull‐In” compound, or  <br />other U.L. approved lubricant.  Flax soap is not approved and not  <br />permitted on the job.  <br />n. Non‐ferrous identifying tags or pressure sensitive labels shall be  <br />securely fastened to all cables, feeders, and power circuits in pull  <br />boxes and manholes.  Tags or labels shall be permanently  <br />stamped or printed to correspond with markings on drawings or  <br />marked so that feeder or cable may be readily identified.  Must be  <br />viewable from 12‐inches.