  <br />  <br />SP 40  <br />  <br />14‐1 GENERAL  <br />14‐1.01 SUMMARY  <br />1.  Manufacturers: As shown on plans and including Franklin Electric, SQD, Schneider  <br />Electric, Wattstopper, LC&D, Hubbell, Leviton, Lutron, Lithonia, Federal Signal,  <br />Liberty, or approved equal.   <br />B.  Electrical System:  All systems shall be lockable.  <br />1. Motor Starter & Alarm Panel.  <br />a.  Supplied as a Type 4x fiberglass dead‐front duplex motor starter  <br />and controls alarm panel UL Labeled from the manufacturer.  <br />b.  Factory tested and labeled as a complete assembly.  <br />c.  Supplied with audio and visual alarms and reset.  <br />d.  Supplied with Liberty controls motor protector and monitoring  <br />controller.  <br />e.  Supplied with manual and automatic lead‐lag controls as shown  <br />on approved project plans.  <br />f.  Provide protected above ground conduit using water‐tight  <br />insulated throat compression EMT and fittings housing a  <br />continuous wire feeder with no splices.  Use RSC in unprotected  <br />area.   <br />g.  Underground feeder wire to be USE‐2/RHW‐2 direct burial rated  <br />installed in PVC‐40 and sloped away from building and sealed at  <br />both ends to keep out water. RSC in unprotected area.   <br />C.  Approvals:  <br />1. Standards and Guidelines:  <br />a. Energy Star, IESNA, IES LM‐79  <br />b. IES LM‐80; UL 8750  <br />c. ISO 9001:2008 Registered.  <br />d. NEMA  <br />e. IEC  <br />f. NEC  <br />g. UL Labeled.  <br />D. Commissioning and Testing:  <br />1. Motor Starter and Alarm Panel:  <br />a. Commissioning (verifications and functional performance):  <br />I. To be performed in coordination with Liberty LSG202M  <br />motor system vendor.  <br />II. Provide logistical support where electrical systems affect  <br />testing; coordinate with vendor as required.