Laserfiche WebLink
10. INSTALLATION <br /> The pump and motor shall be placed and installed in full <br /> accordance with the manufacturer's recommendations and in <br /> accordance with good engineering practice. Great care shall <br /> be exercised in preserving proper alignment and positioning <br /> of the equipment so that it will function quietly and <br /> smoothly. The base plate shall be in full and true contact <br /> with the supporting concrete base without shimming. A mastic <br /> seal shall be provided to the concrete base as required by the <br /> Health Department. <br /> C . HYDROPNEUMATIC PR.sSSURT LEVEL CONTROLS <br /> 1. Function: <br /> As water level falls , pressure decreases . At a preset pressure <br /> (approximately 40 psi ) , PS 1 closes starting pump. The pump <br /> brings up a column of air overcharging the tank. As pumping <br /> continues , pressure increases . At a preset pressure (approxi- <br /> mately 45 psi ) , PS 1 opens but the pump control circuit is sealed <br /> in by PWl and continues pumping. At a predetermined level PR is <br /> energized , stopping the pump. The air bleed off valve opens <br /> at a predetermined pressure (approximately 65 psi ) and bleeds <br /> pressure down to approximately 60 psi . If pressure should drop <br /> below 40 psi (at approximately 30 psi ) PS 3 closes , sounds <br /> alarm and illuminates alarm lamp. Audible alarm is silenced <br /> with momentary push button. <br /> 2. materials : <br /> All materials must be of at least equal quality to those used by <br /> TESCO. Pressure switches shallbe individually enclosed , dust <br /> tight with mercury wetted contacts . Sensing diaphrams and solid <br /> state switch shall have a combined accuracy of one half inch of <br /> water. All relays shall be encapsulated with interchangeable <br /> plug-in cards and shall conform to C .S .A. file number LRX 6377- <br /> 4 D and UL where applicable. .11otor protective devices shall meet <br /> all specific ,fob requirements including time delay relay, <br /> undervoltage protection, _single- phase, ambient compensating, <br /> and very very inverse overcurrent trip on all three legs . Current <br /> transformers , where required, shall be of metering accuracy with <br /> 0.03 burden factor. <br /> 3. Substitutions : <br /> Any additional expense incurred by the owner or engineer for <br /> special reviewing or correcting of submittals , field labor at <br /> start-up as for equipment corrections shall be charged direct <br /> to the Contractor. The manufacturers ' representative shall <br /> field adjust and check operation of the system after installation <br /> at no extra charge. If the substitute materials do not satisfy <br /> the owner in all respects he may, at any time within one year <br /> after date of complete acceptance, elect that they be replaced <br /> with the specified brand equipment at the sole expense of the <br /> Contractor. <br /> (46) <br />