Laserfiche WebLink
KEYED NOTES <br />GENERAL NOTES <br />1.ROUTE NEW CW LINE 5' OUTSIDE BUILDING TO CIVIL <br />STUB-OUT. SEE CIVIL PLANS FOR CONTINUATION. PROVIDE <br />SHUT-OFF VALVE AT BUILDING ENTRANCE. FIELD VERIFY <br />EXACT SIZE AND LOCATION PRIOR TO CONNECTION <br />. <br />2.PROVIDE AND INSTALL INTERIOR TANKLESS WATER HEATER <br />MOUNTED TO WALL PER MANUFACTURERS INSTALLATION <br />INSTRUCTIONS. CONTRACTOR TO PROVIDE AND INSTALL ALL <br />NECESSARY VENT KITS, AND CONTROLLERS FOR WIRING <br />UNITS. VENT KITS PROVIDED BY THE MECHANICAL <br />CONTRACTOR AND INSTALLED BY THE ELECTRICAL <br />CONTRACTOR <br />3.ROUTE FILTERED COLD WATER PIPING DOWN IN WALL TO <br />SERVER FIXTURES IN BAR AREA. <br />4.PROVIDE LAVATORY WITH THERMOSTATIC MIXING VALVE <br />AND SET TO 110° F. <br />5.PROVIDE AND INSTALL TRAP PRIMER IN ACCESSIBLE <br />LOCATION. ROUTE 1/2" CW TO FLOOR DRAIN. <br />6.PROVIDE AND INSTALL RECIRC PUMP WITH COMBINATION <br />AQUA-STAT AND TIMER. <br />7.PROVIDE AND INSTALL SANI-SAVE AND LMENTARY ONE MOP <br />FILLER. SEE DETAIL 10/P4.0. DETERMINE FINAL LOCATION <br />WITH OWNER AND CM PRIOR TO BID AND INSTALLATION. <br />8.PROVIDE AND INSTALL CLICK & CLEAN, SEE DETAIL 11/P4.0. <br />DETERMINE FINAL LOCATION WITH OWNER AND CM PRIOR TO <br />BID AND INSTALLATION. <br />A.EXACT LOCATION OF PLUMBING FIXTURES SHALL BE <br />DETERMINED FROM ARCHITECTURAL DRAWINGS. <br />B.BEFORE SUBMITTING BID, THE PLUMBING CONTRACTOR <br />SHALL REVIEW THE ARCHITECTURAL DRAWINGS AND <br />INCLUDE IN HIS BID AN AMOUNT TO FURNISH AND INSTALL <br />ANY FIXTURES WHICH ARE SHOWN IN ADDITION TO FIXTURES <br />SHOWN ON THE PLUMBING DRAWINGS. <br />C.CONTRACTOR SHALL VERIFY AND COORDINATE LOCATION OF <br />ALL PLUMBING LINES WITH DUCTWORK AND ELECTRICAL <br />SERVICES. <br />D.THE INSTALLATION OF ALL VALVES, UNIONS, <br />THERMOMETERS, GAUGES, OR OTHER INDICATING OR <br />RECORDING EQUIPMENT, OR SPECIALTIES REQUIRING <br />FREQUENT READING, REPAIRS, ADJUSTMENT, INSPECTION, <br />REMOVAL OR REPLACEMENT SHALL BE CONVENIENTLY AND <br />ACCESSIBLY LOCATED WITH REFERENCE TO THE FINISHED <br />BUILDING. <br />E.CONTRACTOR SHALL NOT CUT HOLES IN STRUCTURAL <br />MEMBERS WITHOUT FIRST SECURING WRITTEN APPROVAL <br />FROM THE ARCHITECT. <br />F.CONTRACTOR SHALL INSTALL DIELECTRIC UNIONS AT <br />CONNECTIONS OF DISSIMILAR METALS. <br />G.CONTRACTOR SHALL ROUGH-IN ALL WASTES AND SUPPLIES <br />TO SPECIAL EQUIPMENT ACCORDING TO MANUFACTURERS <br />SHOP DRAWINGS AND MAKE FINAL CONNECTIONS. ALL <br />SUPPLIES SHALL BE VALVED. <br />H.ALL PLUMBING INSTALLATIONS SHALL COMPLY WITH THE <br />CALIFORNIA PLUMBING CODE, NFPA 90, AND ALL LOCAL, <br />STATE, AND FEDERAL ORDINANCES, CODES, LAWS AND <br />REGULATIONS. <br />I.HOT WATER FROM WATER HEATERS SHALL BE SET TO <br />DELIVER OVER 140°F WATER. <br />J.CONTRACTOR TO PROVIDE AND INSTALL MIXING VALVES AT <br />ALL LAVATORIES AND HAND SINKS TO REDUCE 140°F WATER <br />TO 110°F WATER. MIXING VALVES SHALL CONFORM TO ASSE <br />1070. <br />K.PROVIDE ISOLATION BALL VALVE AT EACH BRANCH <br />FIXTURES. <br />L.WHERE CW AND HW PIPING IS SHOWN DOWN IN WALL, <br />COMMON TO MULTIPLE FIXTURES, PROVIDE WATER PIPING IN <br />WALL TO EACH FIXTURE. SIZE PIPING AS INDICATED ON <br />FIXTURE SCHEDULE, PROVIDE AIR CHAMBER ON BOTH CW <br />AND HW AT EACH FIXTURE. <br />M.ROUTE CW, HW, HWC, FW, G, AND V LINES IN CEILING AS HIGH <br />AS POSSIBLE. <br />N.CONTRACTOR TO COORDINATE WITH KITCHEN EQUIPMENT <br />DRAWINGS FOR LOCATIONS AND REQUIREMENTS OF <br />COOKING EQUIPMENT. <br />P2.1 <br />PLUMBING PLAN - <br />DOMESTIC WATER <br />--www.stantec.comTEL. 1383 North McDowell Blvd. Suite 250Petaluma, CA 94954707.765.1660Architecture Inc.R <br />ENGINEERING, INC <br />OBISON <br />19401 40TH AVE W., SUITE 302 <br />LYNNWOOD, WA 98036 <br />206-364-3343 tel <br />CONTACT: MARK MANGLICMOT <br />5/14/21 <br />- <br />1 PLUMBING PLAN - DOMESTIC WATER SCALE: 1/4" = 1'-0"