Laserfiche WebLink
STEP 25. INSTALL WARNING PLATE <br />Bend the three warning plate ears dawn then sllde the <br />tie wrap Mr the blaming piste ears and position warm <br />ing plate against riser pipe approximately 1" below the <br />adaptor. Tighten thetleWrap securely. Thevalveis <br />now fully Installed and In operating position. <br />FiQtpY Z5 <br />5TEP 2iSe YALYE REIroO1fAL <br />The vaHe can be removed For tank leak test ng, Inspec- <br />tton, etc, by removing the Rotatable Product Adaptor, <br />the V nipple, and the lack Screw Kit. Reinstall per the <br />above instructions. <br />For tastable models only: It is not necessary to re- <br />move the valve tocheckpoppetrnovementIfunc ion. <br />See Page 17 for full testing details. <br />SM 27, ELECTRONIC LIQuIO LEVEL MONITORING <br />If an electronic level monitor iF installed, it must be cali- <br />brated to match the top of the 7150 valve body, which <br />must correlate with 95% of the actual tank capacity, <br />Manufaett>Yer: "dI'Vi�' <br />Mader 71 SO,4' <br />{9' repre"nts size) <br />ManufactureDate: <br />'MFG ►lyVIYY' <br />MM =Month YY -Year <br />7R <br />