Laserfiche WebLink
Project No. 10-1768 AdvancedGeo <br /> An Employee-Owned Company <br /> Page 14 of 19 <br /> Storage drums are not refilled, and therefore overfill prevention systems do not apply. <br /> ASTs equipped with liquid level sensing devices are tested on a monthly basis during the <br /> monthly inspection of the Facility, following manufacturer recommendations. Venting <br /> capacity is suitable for the fill and withdrawal rates. Facility personnel are present <br /> throughout the filling operations to monitor the product level in the tanks. <br /> 5.2.9. Effluent Treatment Facilities - 40 CFR 112.8(c)(9) <br /> Storm water within the fuel island is inspected, as deemed necessary by Facility <br /> management, prior to discharge. If deemed not suitable for discharge to the direct surface <br /> sheet flow to the retention pond. <br /> Facility management will decide either to containerize until picked up by a licensed liquid <br /> waste hauling vendor contracted to haul waste oil or discharged into the oil/water <br /> separator which discharges to the to the retention pond. <br /> Manifests for fuel island hauling are kept with this SPCCP for at least three years, unless <br /> otherwise specified. Off-site discharges made by Facility personnel are documented in <br /> Appendix G. <br /> 5.2.10. Visible Discharges - 40 CFR 112.8(c)(10) <br /> Visible discharges from any container or appurtenance — including seams, gaskets, <br /> piping, pumps, valves, rivets and bolts — are quickly corrected upon discovery. Oil is <br /> promptly removed from berm areas and disposed of according to the waste disposal <br /> method described in Section 6.0. of this Plan. <br /> 5.2.11. Mobile and Portable Containers - 40 CFR 112.8(c)(11) <br /> The Facility uses 55-gallon drums which are stored over secondary containment spill <br /> pans or within an area with land-based spill response. <br /> 5.3. TRANSFER OPERATIONS, PUMPING, AND IN-PLANT PROCESSES — <br /> 40 CFR 112.8(d) <br /> Transfer operations at this Facility include: <br /> • Waste oil transfer into the corresponding ASTs. <br /> • The filling of Facility vehicles at the diesel fueling AST via the dispenser. <br /> • The transfer of oil from tanker trucks at the unloading area. <br /> • The transfer of oil to vehicles in the Maintenance Building. <br />