Laserfiche WebLink
A dOAQU1N Environmental Health Department <br /> COUNTY <br /> CP22 - AST Non-Qualified Inspection Report <br /> Facility Name: Facility Address: Date: <br /> MANTECA WQCF 2450 W YOSEMITE AVE, MANTECA Jul 31 2024 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> CORRECTIVE ACTION: Implement the SPCC plan, as required. Submit proof of correction to the EHD. <br /> This is (Class 2)Violation. <br /> 11 Code of Fed Regulations 112.7 4010012-SPCC in writing,follows code seq/cross ref, good eng practice, mgt <br /> approval, items not in place. <br /> OBSERVATION:The Spill Prevention, Control, and Countermeasure(SPCC)Plan reviewed at the time of inspection, <br /> dated 9/19/2019, did not follow the order or requirements of 40 CFR Part 112.7. <br /> 1.The Plan does not follow the required SPCC rule sequence and doesn't include adequate cross-reference. (112.7(a) <br /> (3)(ii-vi) <br /> 2.The Plan does not have the full approval of management at a level of authority to commit the necessary resources <br /> to fully implement the SPCC plan, as specified in the SPCC plan. <br /> REGULATION GUIDANCE: 112.7 If you are the owner or operator of a facility subject to this part you must prepare a <br /> Plan in accordance with good engineering practices. The Plan must have the full approval of management at a level of <br /> authority to commit the necessary resources to fully implement the Plan. <br /> CORRECTIVE ACTION: Ensure that your SPCC Plan complies with the following requirements: <br /> 1. It follows the required SPCC rule sequence and/or includes adequate cross-reference. <br /> 2. Has the full approval of management at a level of authority to commit the necessary resources to fully implement <br /> the SPCC plan. <br /> Provide proof of correction to the EHD. <br /> This is (Minor)Violation. <br /> 30 Code of Fed Regulations 112.7(f)(1)4020001 -Training provided for op/maint of equip, discharge procedures, <br /> laws/regs, general fac ops, and SPCC. <br /> OBSERVATION: It appears that the oil handling personnel were not adequately trained, as required. Facility failed to <br /> provide training to Tim Carroll, Wastewater Maintenance Supervisor and other oil-handling personnel regarding the <br /> following: 1.The operation and maintenance of equipment to prevent discharges. 2. Discharge procedure protocols. 3. <br /> Applicable pollution control laws, rules, and regulations. 4.The contents of the SPCC Plan. <br /> REGULATION GUIDANCE: (f)(1)At a minimum,train your oil-handling personnel in the operation and maintenance of <br /> equipment to prevent discharges; discharge procedure protocols; applicable pollution control laws, rules, and <br /> regulations;general facility operations; and,the contents of the facility SPCC Plan. <br /> CORRECTIVE ACTION: Immediately provide adequate training to all oil handling personnel and submit a copy of the <br /> training log and training content to the EHD. <br /> This is(Class 2)Violation. <br /> 55 Code of Fed Regulations 112.7(e), 112.8(c)(6)4030014-Tanks inspected and tested by qualified person in accordance <br /> with industry standards. <br /> OBSERVATION: Facility failed to ensure that tanks are inspected and tested by an appropriately qualified person in <br /> accordance with industry standards. The ASTs have not been tested and Timothy Carroll and Heather Grove did not <br /> know of inspections/records performed for the ASTs/drums.The SPCC plan specifies inspections on a daily, monthly, <br /> and annual basis. <br /> FA0009494 PR0529613 SCO01 07/31/2024 <br /> EHD Rev.12/06/2021 Page 6 of 8 CP22-AST Non-Qualified OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />