Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMP/UDC TEST <br /> Test Method Developed by r] Manufacturer F Industry Standard 0 Professional Engineer <br /> Test Type 0 Pressure 0 Vacuum F Hydrostatic <br /> Test Equipment Used: INCON <br /> Sump/UDC ID 87 WEST STP 87 EAST STP 91 STP DSL STP <br /> Sump Manufacturer BRAVO BRAVO BRAVO BRAVO <br /> Sump Depth (inches) 70" 70" 70" 70" <br /> Sump Bottom to Top of 18" 18" 18" 18" <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 9:21 9:21 11:23 11:23 <br /> Initial Reading 2.6927 1.3438 3.3977 3.6177 <br /> Test End Time 9:37 9:37 11:38 11:38 <br /> Final Reading 2.6929 1.3435 3.3975 3.6168 <br /> Change in Reading 0.0002 .0003 .0002 .0009 <br /> Pass/Fail Criteria 0.002 .002 .002 .002 <br /> Tightness Test Results E Pass rl Fail F Pass 0 Fail Pass ® Fail Pass © Fail <br /> Sump/UDC ID 87 WEST FILL 87 EAST FILL 91 FILL DSL FILL <br /> Sump Manufacturer BRAVO BRAVO BRAVO BRAVO <br /> Sump Depth (inches) 70" 70" 70" 70" <br /> Sump Bottom to Top of N/A N/A N/A N/A <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 1:10 1:10 12:23 12:23 <br /> Initial Reading 4.0878 5.4155 4.8507 2.7214 <br /> Test End Time 1:25 1:25 12:38 12:38 <br /> Final Reading 4.0881 5.4158 4.8511 2.7201 <br /> Change in Reading .0003 .0003 0.004 0.0013 <br /> Pass/Fail Criteria 002 .002 .002 .002 <br /> Tightness Test Results 0 Pass P7 Fail 0 Pass 57 Fail 0 Pass r Fail r Pass r Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail'and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 3 of 5 <br />