My WebLink
|
Help
|
About
|
Sign Out
Home
Browse
Search
COMPLIANCE INFO_2025
Environmental Health - Public
>
EHD Program Facility Records by Street Name
>
T
>
TRACY
>
3725
>
2300 - Underground Storage Tank Program
>
PR0231417
>
COMPLIANCE INFO_2025
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
2/10/2026 8:22:01 PM
Creation date
3/4/2025 11:38:27 AM
Metadata
Fields
Template:
EHD - Public
ProgramCode
2300 - Underground Storage Tank Program
File Section
COMPLIANCE INFO
FileName_PostFix
2025
RECORD_ID
PR0231417
PE
2361 - UST FACILITY
FACILITY_ID
FA0003780
FACILITY_NAME
TRACY SHELL
STREET_NUMBER
3725
Direction
N
STREET_NAME
TRACY
STREET_TYPE
BLVD
City
TRACY
Zip
95376
APN
21217030
CURRENT_STATUS
Active, billable
QC Status
Approved
Scanner
SJGOV\kblackwell
Supplemental fields
Site Address
3725 N TRACY BLVD TRACY 95376
Tags
EHD - Public
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
65
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMP/UDC TEST (continued) <br /> Test Method Developed by 0 Manufacturer 0 Industry Standard ❑r Professional Engineer <br /> Test Type 0 Pressure El Vacuum El Hydrostatic <br /> Test Equipment Used: INCON <br /> Sump/UDC ID UDC 1/2 UDC 3/4 UDC 5/6 UDC 7/8 <br /> Sump Manufacturer OPw OPw OPw OPw <br /> Sump Depth (inches) 36" 36" 36" 36" <br /> Sump Bottom to Top of 18" 18" 18" 18" <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 10:33 10:06 9:44 10:33 <br /> Initial Reading 1.6985 3.3571 2.5947 7.2923 <br /> Test End Time 10:48 10:21 9:59 10:48 <br /> Final Reading 1.6976 3.3569 2.5951 7.2933 <br /> Change in Reading .0009 .0002 .0004 .0010 <br /> Pass/Fail Criteria .002 .002 .002 .002 <br /> Tightness Test Results 0 Pass ® Fail Pass Fail Pass ® Fail Pass PFajil Sump/UDC ID UDC 9/10 UDC 11/12 UDC 13/14 UDC 15/16 <br /> Sump Manufacturer OPw OPw OPw OPw <br /> Sump Depth (inches) 36" 36" 36" 36" <br /> Sump Bottom to Top of 18" 18" 18" 18" <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 10:06 9:44 10:56 10:56 <br /> Initial Reading 2:4413 6:7415 4:3861 2.6277 <br /> Test End Time 10:21 9:59 11:11 11:11 <br /> Final Reading 2.4413 6.7423 4.3854 2.6275 <br /> Change in Reading .000 .0008 .0007 .0002 <br /> Pass/Fail Criteria 002 .002 .002 .002 <br /> Tightness Test Results F Pass ® Fail El Pass r] Fail 0 Pass r] Fail 0 Pass r Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail'and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 4 of 5 <br />
The URL can be used to link to this page
Your browser does not support the video tag.