642
>
2300 - Underground Storage Tank Program
>
PR0231148
>
COMPLIANCE INFO_2026
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
8/10/2026 3:36:55 PM
Creation date
7/1/2026 1:38:08 PM
Metadata
Fields
Template:
EHD - Public
ProgramCode
2300 - Underground Storage Tank Program
File Section
COMPLIANCE INFO
FileName_PostFix
2026
RECORD_ID
PR0231148
PE
2361 - UST FACILITY
FACILITY_ID
FA0000799
FACILITY_NAME
PARK ST PETROLEUM INC
STREET_NUMBER
642
Direction
N
STREET_NAME
HUNTER
STREET_TYPE
ST
City
STOCKTON
Zip
95202
APN
13906035
CURRENT_STATUS
Active, billable
QC Status
Approved
Scanner
SJGOV\bmascaro
Supplemental fields
Site Address
642 N HUNTER ST STOCKTON 95202
Tags
EHD - Public
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
73
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
The following is an itemized list of CP22 - UST FULL violations that have not been <br /> addressed for PARK ST PETROLEUM INC as of February 24, 2026. <br /> Open violations from May 27, 2025 inspection <br /> Violation#10-2030074-Annual Monitoring System Certification Form to the CUPA within 30 days of <br /> completion of the test. <br /> OBSERVATION:A monitoring system certification and leak detector testing was performed on 5/29/2024. A test <br /> report has not been submitted to the EHD or the California Environmental Reporting System (CERS). <br /> REGULATION GUIDANCE:A copy of the test report must be submitted within 30 days of the test. <br /> CORRECTIVE ACTION: Immediately provide this report to the EHD. <br /> ❑ This violation was corrected ❑This violation will be corrected by(date): <br /> C'k Supporting documents included <br /> Describe actions taken or will be taken to correct violation: RESULTS SENT 7/29/24-SJC Weblink Verification attached. <br /> Please remove this from the violation <br /> Violation#11 -2030048-Sec containment testing conducted per requirements&records kept for 36 mths <br /> (TCR 9d). <br /> OBSERVATION: Secondary containment testing was scheduled to be performed on 7/11/2023. Atest report has not <br /> been submitted to the EHD or the California Environmental Reporting System (CERS). No record of testing was <br /> observed on site. <br /> REGULATION GUIDANCE: Secondary containment testing is required once every 36 months. A copy of the test <br /> report must be submitted within 30 days of the test. <br /> CORRECTIVE ACTION: Immediately schedule this test and provide 48 hours notification to the EHD. <br /> ❑ This violation was corrected ❑This violation will be corrected by(date): <br /> P Supporting documents included <br /> Describe actions taken or will be taken to correct violation: RESULTS SENT -SJC Weblink Verification attached. Please <br /> remove this from the violation <br /> Violation#13-2010017-Spill bucket testing results submitted to the UPA within 30 days of testing. <br /> OBSERVATION: Spill container testing was performed on May 29, 2024 . A test report has not been submitted to the <br /> EHD or the California Environmental Reporting System (CERS). <br /> REGULATION GUIDANCE:A copy of the test report must be submitted within 30 days of the test. <br /> CORRECTIVE ACTION: Immediately provide this report to the EHD. <br /> Page 2 of 6 <br />
The URL can be used to link to this page
Your browser does not support the video tag.